SA E-BUS Controller Technical Guide

Appendix

61

OE265-11 and -14 RH Sensors

OE265-11 & OE265-14 Relative Humidity Sensor Test-

ing Instructions

Use the voltage column to check the Humidity Sensor while connected
to a powered expansion module. Read voltage with meter set on DC
volts.

Place the “-” (minus) lead on the terminal labeled GND and the “+”
lead on the AIN terminal that the Humidity sensor is connected to on
the Analog Input/Output Expansion Module.

OE265 Series RH Sensor Testing

The chart below is used to troubleshoot the OE265-11 and OE265-14
Relative Humidity Sensors.

OE265-11 & OE265-14 Relative Humidity

Transmitters –

Humidity vs. Voltage for 0-5 VDC Sensors

Humidity

Percentage

(RH)

Voltage

@

Input

(VDC)

Humidity

Percentage

(RH)

Voltage

@

Input

(VDC)

0%

0.00

52%

2.60

2%

0.10

54%

2.70

4%

0.20

56% 2.80

6%

0.30

58%

2.90

8%

0.40

60% 3.00

10%

0.50

62%

3.10

12%

0.60

64%

3.20

14%

0.70

66%

3.30

16%

0.80

68%

3.40

18%

0.90

70%

3.50

20%

1.00

72%

3.60

22%

1.10

74%

3.70

24%

1.20

76%

3.80

26%

1.30

78%

3.90

28%

1.40

80%

4.00

30%

1.50

82%

4.10

32%

1.60

84%

4.20

34%

1.70

86%

4.30

36%

1.80

88%

4.40

38%

1.90

90%

4.50

40%

2.00

92%

4.60

42%

2.10

94%

4.70

44%

2.20

96%

4.80

46%

2.30

98%

4.90

48%

2.40

100%

5.00

50%

2.50

Table 5: Humidity/Voltage for OE265-11 & -14
Humidity Sensors