Appendix, Sa e-bus controller technical guide – Orion System SA E-BUS Controller User Manual

Page 63

Advertising
background image

SA E-BUS Controller Technical Guide

Appendix

63

OE275-01 Suction Pressure Transducer Testing

OE275-01 Suction Pressure

Transducer Testing for R410A

Refrigerant

The Evaporator Coil Temperature is calculated by converting the Suc-
tion Pressure to Temperature. The Suction Pressure is obtained by using
the OE275-01 Suction Pressure Transducer, which is connected into the
Suction Line of the Compressor.

Use the voltage column to check the Suction Pressure Transducer while
connected to the SA Expansion Module. The SA E-BUS Controller and the
SA Expansion Module must be powered for this test. Read voltage with
a meter set on DC volts. Place the positive lead from the meter on the
PR OUT terminal located on the SA Expansion Module terminal block.
Place the negative lead from the meter on the ground (GND) terminal
located adjacent to the PR OUT terminal on the SA Expansion Module
terminal block. Use a refrigerant gauge set and/or an accurate electronic
thermometer to measure the temperature or suction line pressure near
where the Suction Pressure Transducer is connected to the suction line.
Measure the Voltage at the terminals PR OUT and GND terminals and
compare it to the appropriate chart depending on the refrigerant you
are using. If the temperature/voltage or pressure/voltage readings do
not align closely with the chart, your Suction Pressure Transducer is
probably defective and will need to be replaced.

See the OE275-01 Suction Pressure Transducer, Pressure, Temperature,
and Voltage Chart for R410A Refrigerant testing (Table 7). The chart
show a temperature range from 20°F to 80°F. For troubleshooting pur-
poses, the DC Voltage readings are also listed with their corresponding
temperatures and pressures.

Table 7: Coil Pressure/Voltage/Temp for OE275-01
Suction Pressure Transducers - R410A Refrigerant

OE275-01 Suction Pressure Transducer Coil

Pressure

– Temperature – Voltage Chart for R410A

Refrigerant

Temper

atur

e

°F

Pr

essur

e

PSI

Signal DC V

olts

Temper

atur

e

°F

Pr

essur

e

PSI

Signal DC V

olts

21.19

80.94

1.8

59.03

168.10

3.2

24.49

87.16

1.9

61.17

174.32

3.3

27.80

93.39

2.0

63.19

180.55

3.4

30.99

99.62

2.1

65.21

186.78

3.5

33.89

105.84

2.2

67.23

193.00

3.6

36.80

112.07

2.3

69.24

199.23

3.7

39.71

118.29

2.4

71.15

205.46

3.8

42.30

124.52

2.5

72.95

211.68

3.9

44.85

130.75

2.6

74.76

217.91

4.0

47.39

136.97

2.7

76.57

224.14

4.1

49.94

143.2

2.8

78.37

230.36

4.2

52.23

149.42

2.9

80.18

236.59

4.3

54.50

155.65

3.0

56.76

161.88

3.1

Advertising