Additional applications, Sa e-bus controller to e-bus module wiring, Sa e-bus controller technical guide 32 – Orion System SA E-BUS Controller User Manual

Page 32: Sa e-bus controller, All comm loop wiring is straight thru, T to t, r to r & shld to shld, 24vac gnd, G - fan on/off only r - 24vac, Jumpers

Advertising
background image

Additional Applications

SA E-BUS Controller Technical Guide

32

SA E-BUS Controller to E-BUS Module Wiring

SA E-BUS Controller to E-BUS Module

Wiring

The SA E-BUS Controller connects to the E-BUS Modules using a modu-
lar HSSC cable. E-BUS Modules require a 24 VAC power connection
with an appropriate VA rating. See Figure 26 below for an example of
E-BUS Controller to E-BUS Module wiring.

The E-BUS Modules can be connected to the SA E-BUS Controller’s
E-BUS port or can be daisy-chained together using HSSC cables.

See Figures 27-28 for specifi c E-BUS Module wiring.

Figure 26: SA E-BUS Controller to E-BUS Module Wiring Diagram

HSSC Cable Connect To

SA E-BUS Controller Port

Line Voltage

All Comm Loop Wiring Is

Straight Thru

24VAC

GND

Local Loop

RS-485

9600 Baud

See Individual Component

Wiring Diagrams For

Detailed Wiring Of Analog

Inputs And Outputs

For Stand Alone Applications,

Connect To System Manager. For Network Applications

Connect To Next Controller And/Or MiniLink PD On Local

Loop.

G - Fan ON/OFF Only

R - 24VAC

Relay Output Contacts
R2 Through R5 May Be User-
Configured For The Following:

Note:

1 - Heating Stages
2 - Cooling Stages
3 - Warm-up Mode Command
(VAV Boxes)
4 - Reversing Valve (Air To Air Heat
Pumps)
5 - Reheat Control (Dehumidification)
6 - Preheater For Low Ambient Protection
7 - Alarm
8 - Override
9 - Occupied
10 - Water Side Economizer

A Total Of 20 Relays Are Available

By Adding Expansion Modules.
Expansion Module Relay Outputs Are
User-Configurable As Listed Above.

Connect FRP Tubing To High Pressure
Port (Bottom Tube) and Route To Static
Pressure Pickup Probe Located In Unit
Discharge. Leave Port Marked “Lo” Open
To Atmosphere

OE271

Static Pressure

Transducer

Splice If Required

Connect To Expansion Module
(When Used)

Connect To Digital Room Sensor - See Digital Room Sensor
Wiring Diagram.

Warning:
24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.

T to T, R to R & SHLD to SHLD

Size Transformer For Correct
Total Load.
SA Controller = 8 VA

SA E-BUS Controller

Note:
All Relay Outputs Are Normally Open And Rated
For 24 VAC Power Only.
1 Amp Maximum Load.

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

Jumpers

Note:
Only One SA Controller is Required Whether The SA Unit is a Single Cabinet Or Dual Cabinet Unit.
Additional Wiring For Dual Cabinet Units is Shown and Noted As Such On The Applicable Single
Cabinet Unit Diagrams.

IC DIGITAL

SENSOR

2

IC

EXPANSION

2

STATIC

PRESSURE

LED BLINK CODES

LED NAME

STATUS1 STATUS2

NORMAL OPERATION

0

1

SAT FAIL

1

2

EAT FAIL

2

2

SPC FAIL

3

2

MECH COOL FAIL

1

3

MECH HEAT FAIL

2

3

FAN PROOF FAIL

3

3

DIRTY FILTER

4

3

WATER FLOW ALARM

6

3

DRAIN PAN ALARM

7

3

EMERGENCY SHUTDOWN

5

3

LOW SAT

1

4

HIGH SAT

2

4

CONT. TEMP COOL FAIL

3

4

CONT. TEMP HEAT FAIL

4

4

PUSH BUTTON OVR

1

5

ZONE OVR

2

5

OUTPUT FORCE ACTIVE

0

6

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

AI7

A01

A02

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= EWT (ENTERING WATER TEMPERATURE SENSOR)
= EAT (ENTERING AIR TEMPERATURE SENSOR)
= NOT USED
= SPACE TEMPERATURE SENSOR SLIDE ADJUST

OR VOLTAGE RESET SOURCE

= WATER SIDE ECONOMIZER VALVE 1A &1B (2-10 VDC)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

ANALOG INPUT

JUMPER

SETTINGS

E-BUS

CONNECTOR

WattMaster Label
#LB102060-01-A

Rev.: 1A

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY
COMMON

SA

CONTROLLER

E-BUS

Orion No.:OE332-23E-VCMX-SA

AAON No.:

V07160