SA Expansion Module Input Wiring

Figure 16: OE333-23-SA – SA Expansion Module Input Wiring

SA Expansion Module

Two different Expansion Modules are available for use with the SA E-
BUS Controller to provide additional inputs and outputs beyond those
found on the SA E-BUS Controller.

The SA Expansion Module ( OE333-23-SA E-BUS Controller) provides
8 Binary Inputs, 4 Analog Inputs, 5 Analog Outputs, and 4 Confi gurable
Relay Outputs. See Figures 16 and 17 for complete wiring details.

Emergency Shutdown - N.C. Input

Drain Pan Overflow A - N.O. Input

Drain Pan Overflow B - N.O. Input

Water Proof of Flow B - N.O. Input

Air Proof Of Flow - N.O. Input

Remote Forced Occupied - N.O. Input

VOUT (0-5V)

0-5V

GND

GND

VIN

VAC OR DC

Water Proof of Flow A - N.O. Input

Dirty Filter - N.O. Input

AI2

AI3

AI4

B 7

I

B 6

I

B 5

I

B 3

I

B 4

I

B 1

I

B 2

I

Modular Cable

Connect To SA E-BUS

Controller

Modular Cable

Connect To Next Expansion

Module (When Used)

24 VAC

GND

Entering Air

Humidity Sensor

Indoor Air

Humidity Sensor

10 VA Minimum Power Required

For SA Expansion Module

WARNING!!

Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-
24VAC. Failure to observe polarity will result in damage to one or more of the
boards. Expansion Module must be wired in such a way that the expansion
module and the controller are always powered together. Loss of power to the
expansion module will cause the controller to become inoperative until power is
restored to the expansion module.

SA Expansion Module

AI1

GND

GND

BI8

See Humidity Sensor Wiring
Details For Complete Wiring
Information.

See Suction Pressure
Transducer Wiring Details For
Complete Wiring Information.

Additional Suction
Pressure Sensor Required
On Dual Units Only.

RD

RD

WH

WH

BK

BK

Suction Pressure

Transducer #1

Suction Pressure

Transducer #2

Splice Wire As Required To Reach
From Transducer Location To
Expansion Module Location

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RELAY 2

RELAY 1

RELAY 3

RELAY 4

RELAY
COMMON

I2C

EXPANSION

I2C

EXPANSION

AO1 = BUILDING PRESSURE CONTROL VFD OR

DAMPER ACTUATOR (0-10 OR 2-10 VDC)

= MODULATING HEATING SIGNAL

(0-10 VDC OR 2-10 VDC)

= MODULATING COOLING/DIGITAL SCROLL

SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)

= RETURN AIR DAMPER ACTUATOR

(0-10 VDC)

= RETURN AIR BYPASS DAMPER ACTUATOR

(0-10 VDC)

= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS

AO2

AO3

AO4

AO5

GND

GND

BI1 = HOOD ON - N.O. INPUT

BI2

BI3

BI4

BI5

BI6

BI7

BI8

= DIRTY FILTER - N.O. INPUT
= PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
= SMOKE DETECTOR - N.C. INPUT
= REMOTE DEHUMIDIFICATION - N.O. INPUT

ANALOG INPUT

JUMPER SETTINGS

MUST BE SET AS

SHOWN FOR

PROPER

OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE

OBSERVED OR THE BOARD

WILL BE DAMAGED

www.orioncontrols.com

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

ANALOG INPUT

JUMPER

SETTINGS

RELAY 1 =

RELAY 3 =

RELAY 2 =

RELAY 4 =

IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)

WattMaster Label

#LB102034-01

NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.

AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)

AI2

AI3

AI4

GND

GND

= INDOOR AIR RH SENSOR (0-5 VDC)
= CO2 (0-10 VDC)
= BUILDING STATIC PRESSURE (0-5 VDC)

= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS

+V

SIG

GND

PR OUT

GND

SUCTION PRESSURE
TRANSDUCER CONNECTION
FOR HVAC UNITS WITHOUT
DIGITAL COMPRESSOR

TO VCM-X INPUT
TERMINALS AI5 & GND

OE333-23-EM-A VCM-X EXPANSION MODULE

WA

RN

IN

G

OB

SE

RV

E

POLAR

IT

Y

SA

AI1 = ENTERING AIR RH SENSOR (0-5 VDC)

AI2

AI3

AI4

GND

GND

= INDOOR AIR RH SENSOR (0-5 VDC)
= SUCTION PRESSURE A (0-5 VDC)
= SUCTION PRESSURE B (0-5 VDC)

= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS

AO1 = MODULATING HEATING SIGNAL

(0-10 VDC OR 2-10 VDC)

= MODULATING COOLING STAGE 1 SIGNAL

(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)

= MODULATING COOLING STAGE 2 SIGNAL

(DIGITAL COMPRESSOR ONLY 1.5-5 VDC)

= WSE BYPASS 2A SIGNAL

(0-10 VDC)

= WSE BYPASS 2B SIGNAL

(0-10 VDC)

= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS

AO2

AO3

AO4

AO5

GND

GND

ANALOG INPUT

JUMPER SETTINGS

MUST BE SET AS

SHOWN FOR

PROPER

OPERATION

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

ANALOG INPUT

JUMPER

SETTINGS

RELAY 1 =

RELAY 3 =

RELAY 2 =

RELAY 4 =

IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)

NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.

BI1 = WATER PROOF OF FLOW - A - N.O. INPUT

= WATER PROOF OF FLOW - B - N.O. INPUT
= AIR PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= EMERGENCY SHUTDOWN - N.C. INPUT
= DRAIN PAN OVERFLOW - A - N.O. INPUT
= DRAIN PAN OVERFLOW - B - N.O. INPUT
= DIRTY FILTER - N.O. INPUT

BI2

BI3

BI4

BI5

BI6

BI7

BI8

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RELAY 2

RELAY 1

RELAY 3

RELAY 4

RELAY
COMMON

I2C

EXPANSION

I2C

EXPANSION

24 VAC
POWER ONLY

WARNING!

POLARITY

MUST BE

OBSERVED OR

THE BOARD

WILL BE

DAMAGED

WattMaster Label

#LB102061-A

Rev.: 1C

SA Expansion Module

Orion No.:OE333-23-SA

AAON No.:

R96180

The 12-Relay Expansion Module ( OE358-23-12R) provides for 12
Dry Contact Confi gurable Relay Outputs. See Figure 25 for complete
wiring details.

The expansion modules can be used individually or together to provide
the required inputs and outputs for your specifi c applications.