Additional Applications

SA E-BUS Controller Technical Guide

34

Two Condenser Head Pressure Module Overview and Wiring

Two Condenser Head Pressure

Module

The Two Condenser Head Pressure Module ( OE370-23-HP2C)
monitors four individual head pressure transducers and controls two
Condenser Fans or Water Valves on units with two physically separate
condenser sections. The highest reading of head pressure transducers
1 & 2 controls Condenser Signal A. The highest reading of head pres-
sure transducers 3 & 4 controls Condenser Signal B.

A pulse width

modulation (PWM) signal is used to control the Condenser Fans. A
0-10 volt output signal is used to control the valves.

Figure 27: Two Condenser Head Pressure Module to E-BUS Distribution Module Wiring Diagram

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

COM

Condenser Fan A

ECM Motor

+

Head Pressure Transducers

0 - 667 PSI

(One Per Refrigerant Circuit)

OE370-23-HP2C

Two Condenser Head Pressure Module

Setting Of OPTIONS

Dip Switch

Not Required When

Used With SA Controller

+5V

SIG 2

GND

OP

T

IO

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

BIN 2

R1

R2

GND

RELAYS

ADDRESS

SIG 3

+5V

GND

BIN 1

COM

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

This Dip Switch Is Not

Used For This Application

PWR

COM

Condenser Fan B

ECM Motor

+

COM

COM

+

+

VFD Condenser A Signal

For Air Cooled

Condenser Applications

VFD Condenser B Signal

For Air Cooled

Condenser Applications

Head Pressure Control

Valve Actuator - A
For Water Cooled

Condenser Applications

Head Pressure Control

Valve Actuator - B
For Water Cooled

Condenser Applications

Connect To The

SA E-BUS Controller

Connect To Other

WattMaster-Approved

E-BUS Expansion Module(s)

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!!
Observe Polarity! All
Boards Must Be Wired
With GND-to-GND And
24 VAC-To-24 VAC.
Failure To Observe
Polarity Could Result In
Damage To The Boards.

HSSC Cable

Use For Dual

Applications Only

Use For

Dual

Applications

Only

Use For

Dual

Applications

Only

3 (Y)

3 (Y)

5 (U)

5 (U)

2 (+)

2 (+)

1 (-)

1 (-)

1 (-)

1 (-)

The Two Condenser Head Pressure Module connects to the SA E-
BUS Controller, allowing the Two Condenser Head Pressure Module
to receive setpoints from the SA E-BUS Controller. See Figure 27
below for wiring diagram.

The Two Condenser Head Pressure Module requires a 24 VAC power
connection with an appropriate VA rating.

NOTE: For complete information, including the sequence of
operation, refer to the Two Condenser Head Pressure Module
Technical Guide
.