Installation & wiring, Relay expansion module overview and wiring, Sa e-bus controller technical guide – Orion System SA E-BUS Controller User Manual

Page 31: Warning

Advertising
background image

SA E-BUS Controller Technical Guide

Installation & Wiring

31

12-Relay Expansion Module Overview and Wiring

EXP1

EXP1

EXP2

EXP2

Set Jumper As Shown
Above When Both The 12
Relay & SA Expansion
Module Are Used

12-Relay

Expansion Module

Set Jumper As Shown
Below When Only The
12 Relay Expansion
Module Is Used

POWER

RLY1

RLY2

RLY3

RLY4

RLY COM

EXP1

EXP2

24VAC

GND

EXPANSION BOARD

YS102228 REV 1

RELAY

RLY5

RLY6

RLY7

RLY8

RLY COM

RLY9

RLY10

RLY11

RLY12

RLY COM

MADE IN USA

SET JUMPER AS
SHOWN WHEN
THE 12 RELAY
EXPANSION MODULE
IS USED

ONLY

SET JUMPER AS
SHOWN WHEN BOTH
THE SA EXPANSION
MODULE AND THE
RELAY EXPANSION
MODULE ARE USED

J1

J1

EXP1

EXP1

EXP2

EXP2

NOTE:
IT IS RECOMMENDED THAT YOU WRITE THE
DESCRIPTION OF THE RELAY OUTPUTS YOU
ARE CONNECTING TO THE RELAY EXPANSION
MODULE IN THE BOXES PROVIDED ABOVE
USING A PERMANENT MARKER (SHARPIE)
FOR FUTURE REFERENCE.

®

WattMaster Label

#LB102043

I2C

EXPANSION

I2C

EXPANSION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE

OBSERVED OR THE BOARD

WILL BE DAMAGED

www.orioncontrols.com

RLY 1 =

RLY 7 =

RLY 2 =

RLY 8 =

RLY 3 =

RLY 9 =

RLY 4 =

RLY 10 =

RLY 5 =

RLY 11 =

RLY 6 =

RLY 12 =

OE358-23-12R-A 12 RELAY EXPANSION MODULE

Configurable Relay Output #9

Configurable Relay Output #1

Configurable Relay Output #5

R9

R1

R5

R10

R2

R6

R11

R3

R7

R12

R4

R8

Configurable Relay Output #10

Configurable Relay Output #2

Configurable Relay Output #6

Configurable Relay Output #11

Configurable Relay Output #3

Configurable Relay Output #7

Configurable Relay Output #12

Configurable Relay Output #4

Configurable Relay Output #8

Relay Output Contacts
R1 Through R12 May Be User-Configured
For The Following:

Note:

-

1 - Heating Stages
2 - Cooling Stages
3 - Warm-up Mode Command (VAV Boxes)
4 - Reversing Valve (Heat Pumps)
5 - Reheat Control (Dehumidification)
6 - Preheater For Low Ambient Protection
7 - Alarm
8 - Override
9 - Occupied
10 - Water Side Economizer

A Total Of 20 Relays Are Available By

Adding Relay Expansion Modules. All
Expansion Module Relay Outputs Are User
Configurable As Listed Above.

Modular Cable

Connect To SA E-BUS Controller

Modular Cable

Connect To Next Expansion Board

(When Used)

24 VAC

GND

15 VA Minimum Power

Required For

OE358-23-12R

12 Relay Expansion Module

WARNING!!

Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or
more of the boards. Expansion Modules must be wired in such a way that the expansion modules and the controller are always powered
together. Loss of power to the expansion module will cause the controller to become inoperative until power is restored to the expansion module.

Note:
All Relay Outputs Are Normally Open
And Rated For 24 VAC Power Only.
1 Amp Maximum Load.

The expansion modules can be used individually or together to provide
the required inputs and outputs for your specifi c applications.

When using the 12-Relay Expansion Module, you must correctly confi g-
ure a set of jumpers on the board depending on whether it will be used
by itself or in addition to the SA Expansion Module.

The jumpers are located on the edge of the 12-Relay Expansion Module
on the same side of the module as the power connection. See Figure
25
below for details regarding setting the switch correctly for your
application.

Figure 25, cont.: OE358-23-12R – 12-Relay Expansion Module Wiring and Jumper Settings

Advertising