Installation & wiring, Sat & remote sat reset signal wiring, Sa e-bus controller technical guide – Orion System SA E-BUS Controller User Manual

Page 13: Space temperature sensor, Remote sat reset signal

Advertising
background image

SA E-BUS Controller Technical Guide

Installation & Wiring

13

GND

TMP

Space Temperature Sensor

OVR

R

E

L

O

C

R

E

M

R

O

A

W

AUX

Wire Required For

Sensors With Slide

Adjust Option Only

Set Jumper For THERM

When Space Sensor Slide

Adjust Is Wired To AI7

AI1

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

Note:
Either The Slide Offset Option For The Space
Temperature Sensor Or The Remote Supply
Air Temperature Reset Signal Option (By
Others) May Be Connected To An AI7 On
The SA E-BUS Controller. Only One Option
Is Allowed, Not Both.

AI1

AI7

GND

SA E-BUS Controller

Note: No Additional Wiring is
Required For Dual Cabinet
Units.

AI7 SET

Figure 8: Remote Supply Air Temperature Reset Signal Wiring

Space Temperature Sensor

The OE210, OE211, OE212, OE213 Space Temperature Sensor is typi-
cally used for constant volume HVAC unit applications controlling one
zone. The Space Temperature Sensor is a 10K Type III thermistor sensor
and should be mounted approximately 5 feet above the fl oor in the space
that is to be controlled. The Space Temperature Sensor is available as a
sensor only, sensor with override button, sensor with slide adjust, and
sensor with slide adjust and override confi gurations.

When the Remote Supply Air Temperature Reset Signal option is needed,
the Slide Offset option on the Room Sensor cannot be used. Only one
of these options may be used on the SA E-BUS Controller.

See Figure 7 below for complete Space Temperature Sensor wiring
details.

Remote Supply Air

Temperature Reset Signal

(By Others)

0-5 VDC or 0-10 VDC Signal

GND

Note:
Either The Slide Offset Option For The Space Temperature
Sensor Or The Remote Supply Air Temperature Reset
Signal Option (By Others) May Be Connected To AI7 On
The SA E-BUS Controller. Only One Option Is Allowed,
Not Both.

Regardless of Whether the Remote

SAT Reset Signal Has Been

Configured For 0-5 or 0-10 VDC,

Jumper Must Be Set For 0-10V

AI7

GND

SA E-BUS Controller

AI1

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

Note: No Additional Wiring
is Required For Dual Cabinet
Units.

AI7 SET

Figure 7: OE210, OE211, OE212, OE213 – Space Temperature Sensor Wiring

SAT & Remote SAT Reset Signal Wiring

Remote SAT Reset Signal

A Remote Supply Air Temperature Reset Signal can be connected to AI7
for applications requiring remote reset of the Supply Air Temperature
Setpoint.

When the Slide Offset option on the Room Sensor is used, the Remote
Supply Air Temperature Reset Signal cannot be used. Only one of these
options may be used on the SA E-BUS Controller.

The SA E-BUS Controller can accept either a 0-5 VDC signal or a 0-10
VDC signal on this input.

See Figure 8 below for complete Remote SAT Reset Signal wiring
details.

Advertising