Installation & wiring, Entering air temperature sensor wiring, Sa e-bus controller technical guide 16 – Orion System SA E-BUS Controller User Manual

Page 16: Entering air temperature sensor, Zone

Advertising
background image

Zone

Zone

Installation & Wiring

SA E-BUS Controller Technical Guide

16

Entering Air Temperature Sensor Wiring

Entering Air

Temperature Sensor

AI4

GND

Be Sure Jumper Is Set

For THERM

On AI4 For Entering

Air Temperature Sensor

AI1

AI1 SET

A

I2 SET

AI3 SET

AI4 SET

A

I5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

SA E-BUS Controller

Mount In Entering

Air Stream

Note: No Additional Wiring
is Required For Dual Cabinet
Units.

Entering Air Temperature Sensor

The OE231 Entering Air Temperature Sensor must be wired as shown
in Figure 11 below for proper operation of the SA E-BUS Controller.
The Entering Air Temperature Sensor is a 10K Type III thermistor sen-
sor. The sensor should be mounted as shown in an area that is protected
from the elements and direct sunlight.

Figure 11: OE231 – Entering Air Temperature Sensor Wiring

NOTE: For Dual Cabinet Units, mount the Entering Air
Temperature Sensor in an Entering Air Duct area that is common
to both SA Units.