Target value input cooling mode

Programming target values

Adaptive cooling and heating function

The input of the target values for summer mode (cooling mode) and the transition mode (heating mode only

for units with HP function) takes place on the user level. The following diagrams provide simplified illustrations

of the operating principles.

Using the SET key, the set value can be displayed during stand-by or

cooling mode. To change the set value, press the SET key for approx. 5

seconds. The display begins to blink. With the or keys the value can

be adjusted within the limits defined at the factory (St 05 + St 06).
St 05 = 10.0 °C

Minimum target value cooling mode

St 06 = 18.0 ℃

Maximum target value cooling mode

Factory setting = 12.5 ℃

min. 5 sec.

short-term

value input

open program

part

short-term

storing

If the temperature at the medium intake exceeds the target
value, the compressor switches on (A) and cooling capacity
is generated. If the calculated operating time of the com-
pressor falls below 3 minutes, an adjustment of the target
value is made. If the calculated operating time is longer
than 3 minutes, the current target value is kept. The me-
dium temperature lowers and the compressor is switched
off when the shut-off point is reached (B).

If the temperature at the medium intake exceeds the
target value, the compressor switches on (A) and heating
capacity is generated. If the calculated operating time of
the compressor falls below 3 minutes, an adjustment of
the target value is made. If the calculated operating time
is longer than 3 minutes, the current target value is kept.
The medium temperature increases and the compressor is
switched off when the shut-off point is reached (B).

Factory setting for target value

St01 = 12.5°C

Factory setting for target value

'St03 = 38.5°C

Adaptive target value

Adaptive target value

Adaptive hysteresis

Adaptive hysteresis

Factory setting for hysteresis

St02 = 3.0°C

Factory setting for hysteresis

St04 = 3.0°C

Compressor ON

Compressor ON

Compressor OFF

Compressor OFF

A

A

B

B

Temperature
Medium intake
through sensor

Pb1

Temperature
Medium intake
through sensor

Pb1

If the programmed target temperature within the system is reached quickly or only a small share of cooling or

heating capacity is accepted by the internal equipment, the operating time of the compressor decreases. An op-

erating time which is too short can have a negative long-term impact on the operation of the unit. The control-

ler continuously calculates the "Adaptive target value SEtr", so that a minimum operating time and minimum

stand-by time of the compressor of 3 minutes can be assured. In the process, the switch-on and shut-off point

of the compressor changes (hysteresis). The unit remains at this operating point until the cooling or heating

capacity accepted in the internal equipment has changed.
The adjustment of the target value has the consequence that the medium temperature can fluctuate beyond

the normal measure depending on the acceptance of the cooling or heating capacity within the system. If this

fluctuation should be decreased, the medium volume should be increased above the minimum medium volume,

e.g. through an additional storage tank.