Connection of the
medium piping

The connection of the lines
on-site takes place on the front
side of the unit.

For the purpose of servicing,
connections must be equipped
with shut-off valves and flow
volumes adjusted using pipe leg
regulating valves.

Additional automatic bleed
valves are to be provided in the
supply and return at the instal-
lation's highest point.

The medium piping may not
exert any structural load on the
unit.

The line connections may not
generate any thermal or me-
chanical stresses on the unit.
If necessary cool line or support
with the second tool.

If the unit is at first to be oper-
ated with only a part of the
entire system, the medium flow
for the missing system compo-
nents is to be simulated using
a pipe leg regulating valve.

The pipe sizing is to be de-
signed so that the required
minimum flow volume is not
under-cut.

A permanent large flow volume
must be ensured to realise the
minimum flow volume.

!

CAUTION

KWL 130(H) - 370(H) with external medium storage tank (accessory)

KWL 130 (H) - 370 (H) with external medium storage tank (hydr. switch)

Pipe routeing
KWL 130(H) - 220(H)

free pipe

routeing

possible

free pipe

routeing

possible

No pipe routeing possible

no pipe

routeing possible

KWL 270(H) - 370(H)

Necessary system components

Diagram of the System components

Legend:

1

Differential pressure switch

2

Dirt trap

3

Shut-off valve

4

Compensator

5

Pressure gauge

6

Draining

7

Manual bleeder

8

Safety valve

9

Circulation pump

10 Valve for hydronic balancing

11 Diaphragm expansion vessel

12 Bleeding valve

13 Medium storage tank (accessory)

KWL 130(H) - 370(H)

REMKO KWL (H)

22