Remko kwl (h), Technical data – REMKO KWL 130 H User Manual

Page 46

Advertising
background image

REMKO KWL (H)

46

Technical data

Series

KWL

130 H

KWL

160 H

KWL

180 H

KWL

220 H

KWL

270 H

KWL

320 H

KWL

370 H

Operating mode

Air-cooled compact chiller with heat pump function

and with the adaptive function for cooling and heating

Nominal cooling capacity

1)

kW

12,9

15,9

18,1

21,8

27,1

31,5

37,2

Nominal heating capacity

2)

kW

14,9

17,5

19,8

24,2

29,9

35,1

39,7

Energy efficiency ratio cooling EER

1)

2,42

2,59

2,57

2,56

2,67

2,67

2,65

Energy efficiency ratio heating COP

2)

2,53

2,60

2,58

2,70

2,80

2,78

2,71

Setting range return temp. Cooling

°C

+10 to +18

Setting range return temp. Heating

°C

+36 to +45

Operating range - cooling

°C

+5 to +45

5)

Operating range - heating

°C

-10 to +20

Operating range cooling (extension)

°C

-15 to +45

6)

Cooling circuits, number

1

Capacity scaling

%

0 / 100

Refrigerant

R 407C

7)

Max. operating pressure, refrigerant

kPa

1900 / 2800

Compressor, number / type

1 / Scroll

Air flow rate, max.

m³/h

9570

9740

10240

10240

11940

11720

16300

Sound pressure level

3)

dB(A)

48,2

48,2

48,7

48,4

48,5

48,6

51,3

Sound power level

dB(A)

79,2

79,2

79,7

79,4

79,5

79,6

82,3

Power supply

V / Hz

400/3~/50

Protection class

IP

24

Elec. power consumption, max.

4)

kW

11,56

12,90

15,03

17,08

18,59

21,94

31,08

Elec. current consumption, max.

4)

A

16,69

18,62

21,70

24,66

26,83

31,67

44,86

Nom. electrical power consumption, cooling

1)

kW

5,33

6,13

7,04

8,51

10,16

11,81

14,02

Elec. nominal current consumption cooling

1)

A

11,45

12,77

16,04

16,96

19,54

22,35

30,06

Nom. electrical power consumption, heating

2)

kW

5,90

6,72

7,68

8,97

10,66

12,64

14,63

Elec. nominal current consumption heating

2)

A

12,15

13,07

16,54

16,98

20,03

23,42

30,70

Elec. starting current, max.

A

72

80

101

126

130

170

183

Operating medium

max. 35% ethylene glycol; max. 35% propylene glycol

Operating limits, medium

°C

+4 to +50

Max. operating pressure, medium

kPa

300

Nominal flow volume, medium C/H

m³/h

2,23

2,74

3,10

3,74

4,64

5,44

6,41

Minimum flow volume, medium

m³/h

1,40

1,80

2,00

2,40

3,00

3,50

4,10

Maximum flow volume, medium

m³/h

3,40

4,50

5,20

6,20

7,80

9,00

10,70

Nominal pump pressure, max.

kPa

207,0

195,0

188,0

177,0

162,0

145,0

175,0

Nominal pressure loss, internal cooling

kPa

38,0

30,1

23,2

31,4

45,0

47,2

58,1

System pressure, available cooling

kPa

169,0

164,9

164,8

145,6

117,0

97,8

116,9

Diaphragm expansion vessel, volume

l

6,0

Diaphragm expansion vessel MAG, preliminary pressure

kPa

150

Medium connection, intake

Inches

1 /1/4 indoors

Medium connection, outlet

Inches

1 /1/4 indoors

Medium content, pipe lines

l

2,1

2,5

3,1

3,7

4,2

4,8

6,4

Minimum medium volume, per unit

l

40,0

47,0

51,0

62,0

80,0

91,0

104,0

Dimensions - height

mm

1115

1215

1300

1300

width

mm

427

532

620

1160

depth

mm

1220

1420

1670

1535

Weight

kg

170,0

176,0

268,0

285,0

325,0

332,0

398,0

Operating weight, approx.

kg

172,1

178,5

271,1

288,7

329,2

336,8

404,4

Standard colour

similar to RAL 9018 / INOX

Serial number INOX

1025...

1026...

1027...

1028...

1029...

1030...

1031...

EDP no. INOX

1650133 1650163 1650183 1650223 1650273 1650323 1650373

Serial number RAL 9018

911...

912...

913...

914...

915...

916...

917...

EDP no. RAL 9018

1650131 1650161 1650181 1650221 1650271 1650321 1650371

1) Air intake temperature TK 35°C, medium intake 12 °C, medium outlet 7 °C, 0% glycol concentration
2) Air intake temperature TK 7°C, medium intake 40 °C, medium outlet 45 °C, 0% glycol concentration
3) Distance 10 m free field
4) Air intake temperature TK 45°C, medium intake 18 °C, medium outlet 15 °C, 0% glycol concentration
5) Crank case heating compressor (standard equipment)
6) Only with winter pressure regulation accessory, set
7) Contains greenhouse gas according to Kyoto protocol

Advertising