REMKO KWL 130 H User Manual

Page 17

Advertising
background image

Fault indicated by code

Code Fault type

Reset

Intake type

Cut-off

Intake value

Automatic

Manual

Digital

Analogue

Softwar

e

parameter

Compr

essors

Condenser

fan

Cir

culation

pump

Anti-fr

eeze

heating, cooling medium

P1

Temperature sensor medium intake defective

PB1

x

x

x

x

x

P2

Temperature sensor medium outlet defective

PB2

x

x

x

x

x

P3

Temperature sensor condenser defective

PB3

x

x

x

x

x

P4

not possible

PB4

x

x

x

x

x

A01

High pressure sensor

HD1/HD2

x

x

x

A02

Low pressure sensor

ND1 <2/hrs <2/hrs

x

x

x

A03

Insufficient temperature medium intake

PB1

x

A04

Insufficient temperature medium outlet

PB2

x

A05

Excessive temperature condenser

x

x

x

A06

Excess temperature condenser

<2/hrs <2/hrs

x

x

x

A07

Anti-freeze protection has responded

x

x

x

x

A08

Differential pressure switch has responded

<2/hrs <2/hrs

x

x

x

x

A09

Excess temperature compressor 1

x

A10

Excess temperature compressor 2

x

A11

Excessive temperature condenser fan

x

A12

Defrosting period exceeded

x

dF07

A13

Maintenance interval compressor 1

Co14

500 hrs

x

A14

Maintenance interval compressor 2

Co15

500 hrs

x

A15

Maintenance interval circulation pump

Co16

500 hrs

x

EE

EEPROM defective

x

x

x

x

x

x

ACF1 Configuration error

x

x

x

x

x

x

ACF2 Configuration error

x

x

x

x

x

x

ACF3 Configuration error

x

x

x

x

x

x

ACF4 Configuration error

x

CF28

x

x

x

x

AFr

Power supply

x

x

x

x

x

x

Reset

1. Faults with automatic reset:

The resetting of the alarm takes place automatically.

2. Faults with manual reset:

The resetting of the alarm can only be carried out by a specialist after the fault has been corrected.

3. Faults with semi-manual reset: The reset is first carried out automatically, afterwards only a manual reset is possible by a specialist,

after the fault has been corrected.

Fault

Code

Possible cause

check

Remedial measures

The unit

does not

start or

switches

itself off.

ACF1

Configuration error

The unit was configured with HP

function but without reversing valve.

Have specialist check regulation or

parameters.

ACF2

Configuration error

No configuration of the condenser

controller. Check parameters CF01

+ FA02

Have specialist check regulation or

parameters.

ACF3

Configuration error

2 digital inputs have the same function Have specialist check regulation or

parameters.

ACF4

Configuration error

Digital input not configured.

Check parameters CF28 + CF07.

Have specialist check regulation or

parameters.

AFr

Frequency alarm

The mains frequency lies beyond the

the permissible range

Have the mains supply checked

by a specialty firm

EE

EEprom controller error

Does the controller operate properly?

Have specialist check regulation or

parameters.

Malfunctions

17