REMKO KWL 130 H User Manual

Page 19

Advertising
background image

Wind

3 Windbreak

20 cm

Snow

4 Minimum clearance to snow

Wall openings

We recommend that the inside

of the opening be padded or

lined for example with a PVC

pipe to prevent damage to the

lines.

After installation, the wall

opening should be closed off

with a suitable sealant. Do not

use materials containing cement
or lime!

Installation material

The unit is fastened on vibration
dampers (accessories) to the floor
by means of bolts. The carrying
capacity of the console and the
wall must be taken into account
when fastening to the wall.

Selection of the installation
location

The unit is designed for horizontal

installation on a base in outdoor

areas. The installation site must

be level, flat and firm. The unit

should also be secured to prevent

toppling.
The unit can be installed outside as

well as inside a building.
In the case of outdoor installation,

please follow the instructions given

below to protect the unit against

the weather.

Rain
The unit should be at least 10 cm

off the ground when mounted on

the roof or ground. when mounted

on the roof or ground.
For cooling and heating units (only

HP-function) elevated installation

increases the generated heat

capacity.

Sun
The finned condenser gives off

heat in cooling mode.

Exposure to sunlight further

increases the temperature of the

fins and reduces the heat released

by the finned heat exchanger.
The unit should, whenever

possible, be installed on the north

side of the building.
If necessary, take measures

to provide sufficient shade

(responsibility of customer).
This can be accomplished with

a small roof covering.
However, the discharging warm air

flow may not be affected by the

measures.

Wind
If the unit is being installed where

it is windy, care must be taken that

the discharged warm air is carried

off in the prevailing wind direction.

If this is not possible, it may be

necessary to install a windbreak

on-site (Figure 3).
Ensure that the windbreak does

not adversely affect the air intake

to the unit.

Snow
The unit should be wall-mounted

in areas of heavy snowfall.
Installation should then be at

least 20 cm above the expected

level of snow to prevent snow

from getting into the outdoor unit

(Figure 4)

.

Installation inside buildings

Ensure that heat can dissipate

adequately when placing the

outdoor unit in cellars, attics,

adjoining rooms or halls (figure 5).

Install an additional fan with

the same air flow as that

of the outdoor unit being

installed in the room which

can compensate any additional

pressure losses with ventilation

ducts (Figure 5, Page 20).

Ensure a continuous and

unobstructed air flow from

outside, preferably using

sufficiently large air openings

(Figure 5, Page 20)

.

Cooling or heating perform-
ance changes as a conse-
quence of the ambient condi-
tions influenced by rain, sun,
wind, and snow.

NOTE

19

Advertising