REMKO KWL 130 H User Manual

Page 9

Advertising
background image

Key functions

/Key

Activate and/or deactivate the unit with the key

by pressing it for longer than 5 seconds. On the display screen

the current display of the the return temperature is shown.

short-term

External enabling

If a potential-free contect is used for the external enabling of the unit,

the controller shows "OFF" in the display and the display of the decimal

places blinks.

The unit has three modes: Stand-By mode, summer mode (cooling mode)

and transition mode (heating mode only for units with HP function). In

stand-by mode the stand-by display illuminates and the current values

are shown. All fault reports and anti-freeze protection resistors are active.

Attention: By changing the parameterisation a different functional

meaning of the display can be programmed!

Mode setting

External contact

Enable open

Display of the current operating values

The normal display shows the current medium intake temperature and

the medium outlet temperature.
By pressing the key the condenser temperature (P63) can also be

read.

normal

display

temperature

medium intake

short-term

short-term

condenser

temperature.

short-term

temperature

medium outlet

normal

display

The potential-free contact has precedence over operation through the con-

troller. With the parameter CF 16 a negation of the contact can take place.
factory. Setting:

CF 16 = 0 (open contact = controller on)

Possible change:

CF 16 = 1 (closed contact = controller on)

External contact

Enable closed

min. 5 sec.

min. 5 sec.

min. 5 sec.

HEATING MODE

only KWL...H

COOLING

MODE

KWL and

KWL...H

Cooling mode

Heating mode

Operating mode

Stand-By

min. 5 sec.

min. 5 sec.

min. 5 sec.

9