Remko kwl (h) – REMKO KWL 130 H User Manual

Page 16

Advertising
background image

Fault

Code

Possible cause

check

Remedial measures

The unit

does not

start or

switches

itself

off.

Mains failure

Does all other electrical

equipment function correctly?

Check voltage and if necessary

wait until turned on again.

Unit's breaker/mains switch

turned off

Is voltage available to the unit?

Switch on unit's breaker/ main

circuit breaker

Wait time too short

Is the compressor icon flashing?

Plan for longer wait period.

Mains current has incorrect

direction of rotation.

Has the phase sequence relay

switched?

Change direction of rotation.

Controller is not working

Is the icon for cooling mode,

heating mode or Stand-By mode

illuminated?

Energise and select operating

mode.

Return temperature or

parameter setting wrong

Check setting.

Change setting.

OFF

No alarm / fault

Check the closed

contact "external enabling"

Open / close

the contact being used.

P1

Medium intake sensor defective Check resistance at PB1

Replace defective sensor.

P2

Medium outlet sensor defective

Check resistance at PB2

Replace defective sensor.

P3

Condenser sensor defective

Check resistance at PB3

Replace defective sensor.

P4

Outdoor temperature sensor defective Check resistance at PB4

Replace defective sensor.

A01

High pressure fault

Heat mode set?

Set summer mode (cooling

mode).

High pressure fault

Are the fans turning?

Is the condenser's air intake free

of obstacles?

Have checked by a specialist.

A02

Low pressure fault

Is the pressure in the cooling

circuit OK?

Have checked by a specialist.

A05

Excessive temperature

condenser

Are the fans turning?

Is the condenser's air intake free

of obstacles?

Have checked by a specialist.

A06

Excess temperature condenser

Have the operating temperatures

been exceeded?

Shut down the system.

A07

Anti-freeze protection has

responded

Is the supply temperature greater

than or less than 4°C?

Increase return temperature,

Increase medium flow,

Set anti-freeze protection temp..

Medium volume in the system

too low

Has the minimum medium

volume been complied with?

Comply with minimum medium

volume e.g. in the reservoir.

A08

Differential pressure switch /

Flow monitor

has responded

Are the following points

OK:

- Medium flow

- No air in the medium lines

- Capacity of the circulation pump

- Does the differential pressure

flow monitor switch

- Shut-off devices open

- Medium pressure to low

Have checked by a specialist.

A12

Fault defrosting

Maximum defrosting duration

exceeded

Have checked by a specialist.

A13

Compressor 1 maintenance

Maintenance interval compressor

1 has been reached (500 op.hrs.)

After maintenance by a specialist reset

of the operating hours see chapter

"Querying the operating status".

A14

Compressor 2 maintenance

Maintenance interval compressor

2 has been reached (500 op.hrs.)

After maintenance by a specialist reset

of the operating hours see chapter

"Querying the operating status".

A15

Circulation pump maintenance

Circulation pump maintenance

interval has been reached

(500 op.hrs.)

After maintenance by a specialist reset

of the operating hours see chapter

"Querying the operating status".

Malfunctions

REMKO KWL (H)

16