Operating structure, Standard display change target values, Param.level 2 with password – REMKO KWL 130 H User Manual

Page 13: Display target values, Menu without password, Param.level 1 without password, Display of current values

Advertising
background image

Operating structure

> 5 sec.

< 2 sec.

< 2 sec.

> 5 sec.

< 2 sec.

< 2 sec.

< 2 sec.

< 2 sec.

> 5 sec.

+

+

/

/

Open configuration

Value/parameter up

Open submenu/value

Close configuration

Value/parameter down

Close submenu

+
+

Standard display

Change target values

C/H target value change

Value change in cooling

between 10.0 and 18.0 and in

heating between 36.0 and 43.0

with the key /, save with

"SET".

Param.level 2 with password

All parameters

Input

Password

All parameters of

the Submenus:

St, CF, Sd, ES, CO,

Ar, dF

Display target values

Display target value cooling

Current target value in cooling mode

Display target value heating

Current target value in heating mode

Menu without password

Current fault list

currently pending, non-

resettable faults are displayed

with "no", resettable faults are

displayed with "rSt"; resetting

with the SET key.

Operating hours compressor 1

Value in hours, resettable after

maintenance, etc. by pressing the

SET key (5 sec.).

Parameter backup to

hotkey

Using a plugged-in hotkey

the current parameters of the

controller can be transferred to

the hotkey.

Operating hours compressor 2

Value in hours, resettable after

maintenance, etc. by pressing the

SET key (5 sec.).

Reset fault list

Faults are displayed in the

sequence n01 (oldest) to n50

(most recent). Through input of

the password under "ArSt" the

list can be reset.

Pump operating hours

Value in hours, resettable after

maintenance, etc. by pressing

the SET key (5 sec.).

Defrosting period

Value in min. and sec. until the

next defrosting interval

Param.level 1 without password

St 01 Target value cooling

St 02 Hysteresis cooling

St 03 Target value heating

St 04 Hysteresis heating

St 09 Output range

Pr2 Password
CF 16 ID 5 Configuration

CF 24 Pb 1 Shut-off

CF 25 Pb 2 Shut-off

CF 26 Pb 3 Shut-off

CF 27 Pb 4 Shut-off

CF 28 Unit active/operating mode

CF 29 Autom. changeover target value

CF 30 Hysteresis changeover

CF 31 Cooling / heating display icon

CF 32 °C/°F conversion

CF 37 Company version

Pr2 Password
Sd 01 Dyn. target value configuration

Sd 02 Shut-off dyn. target value C

Sd 03 Shut-off dyn. target value H

Sd 04 Outside temp. sensor target value C

Sd 05 Outside temp. sensor target value H

Sd 06 Outside temp. sensor hysteresis C

Sd 07 Outside temp. sensor Hysteresis H

Pr2 Password
ES 01 Switch-on time

ES 02 Shut-off time

ES 03 Activation Monday

ES 04 Activation Tuesday

ES 05 Activation Wednesday

ES 06 Activation Thursday

ES 07 Activation Friday

ES 08 Activation Saturday

ES 09 Activation Sunday

ES 10 Target value cooling

ES 11 Hysteresis cooling

ES 12 Target value heating

ES 13 Hysteresis heating

Pr2 Password

Ar 03 Target value anti-freeze protection fault C

Ar 04 Hysteresis anti-freeze protection fault C

Ar 08 Target value anti-freeze protection heating C

Ar 09 Target value anti-freeze protection heating H

Ar 10 Target value cooling W/W

Ar 11 Hysteresis cooling W/W

Ar 12 Hysteresis heating W/W

Ar 13 Config. anti-freeze protection heating

Ar 14 Config. Cooling

Ar 20 E-heating active/operating mode

Ar 21 Target value air temp. active

Ar 22 Hysteresis air temp. active htg

Ar 24 After-run time E-heating 2

Ar 25 Target value air temp. active compr.

Ar 26 Target value air temp. locked compr.

Ar 27 Target value anti-freeze protection fault H

Ar 28 Hysteresis anti-freeze protection fault H

Ar 29 Target value external pump W/W

Ar 30 Hysteresis external pump W/W

Ar 31 Pump active/operating mode

Ar 32 Pump active/operating mode

Pr2

Password

dF 02 Defrosting input parameter

dF 03 Target value defrosting start

dF 04 Target value defrosting end

dF 05 Min. operating time before

defrosting start

dF 06 Minimum defrosting time

dF 07 Maximum defrosting time

dF 10 Min.time defrosting interval

dF 11 Target value defrosting begin (df 10)

dF 12 Target value defrosting (dF 10)

dF 16 Active fault low temperature

dF 19 Target value forced defrost. begin

dF 20 Hysteresis forced defrost. begin

Pr2

Password

Pr2 Password

Pr2 Password

Pr2 Password

All open

parameters

Target values

Configuration

Dyn. target value

Energy-saving

cycle

Compressor

Fan

Anti-freeze

protection

Faults

Defrost

Display adaptive target value

Current, adaptive target value

Display of current values

Medium outlet display

Current value (supply)

Medium intake display

Current value (return)

Condenser display

Current value of condenser tem-

perature or pressure (with winter

pressure controller accessory)

13