Trouble-shooting and customer service – REMKO KWL 130 H User Manual

Page 15

Advertising
background image

The unit has been manufactured using state-of-the-art production methods and tested several times to ensure its
correct function. If malfunctions should occur, please check the unit as detailed in the list below. For installations with
an indoor unit and outdoor unit, observe the chapter "Troubleshooting and customer service" in both operating
manuals.
Please inform your dealer if the unit is still not working correctly after all the function checks have been performed.

Trouble-shooting and customer service

Malfunctions

Please note that this troubleshooting table continues on the next page

Fault

Effect

Possible cause

Remedial measures

The unit

does not

start

Display is not illuminated

No power supply

Check the current connections at the

general supply terminals and the voltage

values.

Check breaker switches/fuses at the

secondary side of the supplemental

transformer.

Incorrect phase sequence.

The KA3 phase sequence relay

did not enable.

Replace current supply phase conductor at

the terminal strip on the switch panel.

The display is illuminated but

he unit does not start

Unit in STAND BY

See paragraph "Key functions" for the

activation of the system.

The display shows OFF

No external enabling

Check connection to terminals 2-3

(external enabling).

The unit does not start, the

compressor icon in the display

is flashing.

Delay time

Wait out the delay time (max 360 sec.),

the compressor should then start.

The lower display flashes

and alternately shows an

alphanumeric code and the

temperature value.

One or more protective

devices have responded

Check which safety device has responded,

correct the cause of the fault and reset the

safety device (see "Fault display").

Compressor protection is

defective.

Does the compressor icon light

up and does the protection

have voltage?

Have specialist replace protection or

compressor.

The unit

is working

with

reduced

cooling/

heating

capacity

Thermal load was increased.

Have structural modifications

been made?

Maintain safety clearances.

Supply temperature too high.

If the supply temperature is

approx. 5 ... 10 ℃?

Reduce return temperature

Air in the medium circuit

Are automatic bleeders

installed at the highest point?

Vent manually or install automatic

bleeders.

Condenser temperature too

high.

Are the fins clean and the

operating limits adhered to?

Clean fins, provide shade for the unit,

adhere to operating limits

Incorrect parameter setting.

Check setting.

Change setting.

Pulse mode because of too

little demand.

Is the system oversized?

Increase medium flow with the installation

of a storage tank.

Medium

discharge

Leak in the lines or insulation

defective.

Are there leaks and are all of

the lines insulated?

Seal and insulate.

Defrosting phase in heating

mode.

Heating mode set?

Normal operating status.

15