Technical data

Series

KWL

130

KWL

160

KWL

180

KWL

220

KWL

270

KWL

320

KWL

370

Operating mode

Air-cooled compact chiller with adaptive function

for cooling

Nominal cooling capacity

1)

kW

12,9

15,9

18,1

21,8

27,1

31,5

37,2

Energy efficiency ratio cooling EER

2,42

2,59

2,57

2,56

2,67

2,67

2,65

Setting range return temp. Cooling

°C

+10 to +18

Operating range - cooling

°C

+15 to +45

Operating range cooling (extension)

°C

+5 to +45

5)

/ -15 to +45

6)

Cooling circuits, number

1

Capacity scaling

%

0 / 100

Refrigerant

R 407C

7)

Max. operating pressure, refrigerant

kPa

1900 / 2800

Refrigerant, basic quantity per cooling circuit

kg

2,74

3,65

7,31

7,53

8,02

10,13

10,51

Compressor, number / type

1 / Scroll

Air flow rate, max.

m³/h

7300

6560

9600

9600

11500

11300

15700

Sound pressure level

3)

dB(A)

45,0

45,0

48,7

48,4

48,4

48,5

51,3

Sound power level

dB(A)

76,0

76,0

79,7

79,4

79,4

79,5

82,3

Power supply

V / Hz

400/3~/50

Protection class

IP

24

Elec. power consumption, max.

4)

kW

8,98

10,22

13,03

14,90

16,15

19,27

26,19

Elec. current consumption, max.

4)

A

14,41

16,45

20,92

23,94

25,90

30,94

42,03

Nom. electrical power consumption, cooling

1)

kW

5,33

6,13

7,04

8,51

10,16

11,81

14,02

Elec. nominal current consumption cooling

1)

A

11,45

12,77

16,04

16,96

19,54

22,35

30,06

Elec. starting current, max.

A

69

77

101

126

130

170

182

Operating medium

max. 35% ethylene glycol; max. 35% propylene glycol

Operating limits, medium

°C

+4 to +18

Max. operating pressure, medium

kPa

300

Rated flow volume, medium - cooling

m³/h

2,23

2,74

3,10

3,74

4,64

5,44

6,41

Minimum flow volume, medium

m³/h

1,40

1,80

2,00

2,40

3,00

3,50

4,1

Maximum flow volume, medium

m³/h

3,40

4,50

5,20

6,20

7,80

9,00

10,70

Nominal pump pressure, max.

kPa

207,0

195,0

188,0

177,0

162,0

145,0

175,0

Nominal pressure loss, internal cooling

kPa

38,0

30,1

23,2

31,4

45,0

47,2

58,1

System pressure, available cooling

kPa

169,0

164,9

164,8

145,6

117,0

97,8

116,9

Diaphragm expansion vessel, volume

l

6,0

Diaphragm expansion vessel MAG, preliminary pressure

kPa

150

Medium connection, intake

Inches

1 /1/4 indoors

Medium connection, outlet

Inches

1 /1/4 indoors

Medium content, pipe lines

l

2,1

2,5

3,1

3,7

4,2

4,8

6,4

Minimum medium volume, per unit

l

40,0

47,0

51,0

62,0

80,0

91,0

104,0

Dimensions - height

mm

1115

1215

1300

1300

width

mm

427

532

620

1160

depth

mm

1220

1420

1670

1535

Weight

kg

165,0

168,0

255,0

270,0

310,0

325,0

380,0

Operating weight, approx.

kg

167,1

170,5

258,1

273,7

314,2

329,8

386,4

Standard colour

similar to RAL 9018 / INOX

Serial number INOX

1010...

1011...

1012...

1013...

1014...

1015...

1016...

EDP no. INOX

1650132 1350162 1650182 1650222 1650272 1650322 1650372

Serial number RAL 9018

870...

871...

872...

873...

874...

875...

876...

EDP no. RAL 9018

1650130 1650160 1650180 1650220 1650270 1650320 1650370

1) Air intake temperature TK 35°C, medium intake 12 °C, medium outlet 7 °C, 0% glycol concentration
2) Air intake temperature TK 7 °C, medium intake 45 °C, medium outlet 50 °C, 0% glycol concentration
3) Distance 10 m free field
4) Air intake temperature TK 45 °C, medium intake 18 °C, medium outlet 15 °C, 0% glycol concentration
5) Only with compressor crank case heating accessory
6) Only with winter pressure regulation accessory, set
7) Contains greenhouse gas according to Kyoto protocol

Advertising