3 - Electrical Connections

3.3.1 POWER SUPPLY

B

Switching power supply with mul-
tiple isolation and PTC protection.
• Standard version:

Nominal voltage:
100... 240Vac (-15...+10%);
Frequency 50/60Hz.

• Low Voltage version:

Nominal voltage:
24Vac (-25...+12%);
Frequency 50/60Hz
or 24Vdc (-15...+25%);
Power consumption 5W max.

L

N

25

26

PTC

included

Supply

27

3.3.2 PV CONTROL INPUT

B

A L-J-K-S-R-T-B-N-E-W thermocouple type
• Connect wires with the polarity as shown;
• Always use compensation cable of the correct type

for the thermocouple used;

• The shield, if present, must be connected to ground.

B For Pt100 resistance thermometer
• If a 3 wires system is used, always use cables of the

same section (1mm

2

min.), maximum line resistance

20

Ω/line.

• When using a 2 wires system, always use cables of the

same section (1.5mm

2

min.) and put a jumper between

terminals 11 and 12

C For

T (2x RTD Pt100) Special

A

When the distance between the controller and the
sensor is 15m, using a cable of 1.5mm

2

section, pro-

duces an error on the measure of 1°C.

R1 + R2 must be <320

Wire resistance

150

Ω max.

Only for two wires

system, put a
jumper between ter-
minals 11 and 12.

Use wires of the
same length and 1.5
mm

2

size.

Maximum line resis-
tance 20

Ω/line.

10

11

12

A

B

A

R2

R1

10

11

12

A

b

B

11

12