Super Systems X5 User Manual

Page 18

Advertising
background image

18

3 - Electrical Connections

3.3.6-F1 DOUBLE ACTION

DIGITAL/DIGITAL CONTROL OUTPUT

B

Cool

load

Static
Relay

20

21

OP6

Notes for pages 17 - 18 - 19
OP1 - OP2 Relay output

• SPST Relay N.O., 2A/250 Vac (4A/120Vac)

for resistive load,

• Fuse 2A ac T at 250V, 4A ac T at 110V.

OP1 - OP2 Triac output
• N.O. contact for resistive load of up to

1A/250 Vac max.

• Fuse 1A ac T
Isolated digital outputs OP5-OP6
• 0…24Vdc, ±20%, 30 mA max.
Isolated analog outputs OP5-OP6
• 0/4…20mA, 750

Ω / 15V max.

0/1…5V, 0…10V, 500

Ω / 20mA max.

[1] Varistor for inductive load 24Vac only

3.3.6-E1 DOUBLE ACTION

DIGITAL/RELAY (TRIAC) CONTROL OUTPUT

B

3.3.6-E2 DOUBLE ACTION

ANALOG/RELAY(TRIAC) CONTROL OUTPUT

B

8

9

OP5

Heat
load

mA mV,V

Heat

load

Static
Relay

8

9

OP5

Fuse

Coil of the cool
load contactor

32

33

OP2

[1]

Fuse

Coil of the cool
load contactor

32

33

OP2

[1]

Heat

load

Static
Relay

8

9

OP5

X5-SSI-uk 18-03-2009 17:53 Pagina 18