TECHNICAL SPECIFICATIONS

Total configurability
(see chapter 4.3 page 25)

PV Input
(see pages13,14
and page 26)

Features
at 25°C env. temp.

Description

From keypad or serial communication the
user selects:
- the type of input

- the type of Setpoint
- the type of control algorithm
- the type of output

- the type and functionality of the alarms
- control parameter values

- access levels

Common
characteristics

A/D converter with resolution of 160,000 points
Update measurement time: 50 ms
Sampling time: 0.1… 10.0 s Configurable
Input shift: - 60… + 60 digit
Input filter with enable/disable: 0.1… 99.9 seconds

Accuracy

0.25% ±1 digits for temperature sensors
0.1% ±1 digits (for mV and mA)

Between 100…240Vac
the error is minimal

Resistance thermometer
(for

∆T: R1+R2 must be

<320

Ω)

Pt100

Ω a 0°C (IEC 751)

°C/°F selectable

2 or 3 wires connection
Burnout (with any combination)

Max. wire Res: 20

Ω max. (3 wires)

Input drift: 0.1°C/10° T

env

<0.1°C/10

Ω Wire Res.

Thermocouple

L, J, T, K, R, B, N, E, W3, W5
(IEC 584)
Rj >10M

°C/°F selectable

Internal cold junction
compensation con NTC
Error 1°C/20°C ±0.5°C
Burnout

Line:

150

Ω max.

Input drift: <2µV/°C. T

env.

<5µV/10

Ω Wire Res.

DC input (current)

4... 20mA, 0... 20mA

Rj =30

Burnout. Engineering units
conf. decimal point position
with or without

√—

Init. Scale -999… 9999
Full Scale -999… 9999
(min. range of 100 digits)

Input drift: <0.1%/20°C T

env.

<5µV/10

Ω Wire Res.

DC input (voltage)

0... 50mV, 0... 300mV Rj >10M

1... 5, 0... 5, 0... 10V

Rj>10k

Frequency (option)
0... 2,000/0... 20,000Hz

Low level

≤2V

High level 4... 24V