Super Systems X5 User Manual

Page 21

Advertising
background image

3.3.10 PROFIBUS DP (OPTION)

B

21

3 - Electrical Connections

DP

DN

DG

VP

1

2

3

4

• Galvanic isolation 500 Vac/1 min
• Compliance to the EIA RS485

standard for PROFIBUS DP;

• Connecting cable: twisted

pair cable as per PROFIBUS
specifications (e.g. Belden
B3079A);

• Max. lenght: 100 m at 12 Mb/s

Termination resistors 220

Ω and

390

Ω (

1

/

4

W, ±5%) for external

mounting on the first and end-
ing PROFIBUS stations only.

Detailed information concerning wiring and cables can be found on
the PROFIBUS Product Guide on Internet at:
http://www.profibus.com/online/list

DP

DN

DG

VP

Initial
PROFIBUS
station

DP

DN

DG

VP

Other
PROFIBUS
stations

DP

DN

DG

VP

Ending
PROFIBUS
station

220

390

390

220

390

390

33

4-40UNC-2B

5

9

6

1

To make the connections easier, a D-Sub type (9 poles)
connector, model AP-ADP-PRESA-DSUB/9P is provided
Must be used with a 9PIN male ERNI type part no. 103648 or sim-
ilar connector.

X5 D-SUB 9 poles

Signal

Description according to

PROFIBUS specifications

4

1

3

RxD/TxD-P (DP)

Receive data/transmission
data plus

6

2

8

RxD/TxD-N (DN)

Receive data/transmission
data negative

VP (VP)

3

5

DGND (DG)

Data transmission potential
(ground to 5V)
Supply voltage of the termi-
nating resistance-P, (P5V)

X5-SSI-uk 18-03-2009 17:53 Pagina 21