4 - Operation

4.5.2 ALARM MENU
(see also pages 32 and 33)

Asymmetric
upper alarm

hysteresis

Asymmetric
lower alarm

hysteresis

The parameter can be set
between 0 and 5% of the con-
figured Span and set in
Engineering units. e.g.
Range =

-200…600°C

Span

= 800°C

Max. Hysteresis = 5% 800°= 40°C

For symmetrical hysteresis set

#hy-d

=

#hy-u

#hy-d

#hy-u

Alarm
delay

Delay time for alarm activation.

OFF

: alarm activated immediately

1...9999 seconds: alarm acti-
vated only if the condition per-
sists for the set time

#tF1

4.5.1 SETPOINT MENU

If SR starting point is lower
than the ending point, both
expressed in engineering units:

If SR starting point is higher
than the ending point, both
expressed in engineering units

Working Setpoint (SP) as com-
bination of Local Setpoint (SL)
and remote signal
Setpoint

Loc.t

(table 3, page 27)

Setpoint

reM.t

(table 3, page 27)

E.g.: Local Setpoint (SL) with an

external Trim with multiply-
ing coefficient of 1/10:

Setpoint type =

Loc.t

rtio

= 0.1;

biaS

= 0

Remote Setpoint (SR) with an
internal Trim with multiplying
coefficient of 1/5:
Setpoint type =

reM.t

rtio

= 0.2;

biaS

= 0

Remote Setpoint range equal to
the Input range:
Setpoint type =

Loc.t

rtio

= 1;

biaS

= LR

SL

= 0

biaS

=

starting point = a

rtio

=

E.g.: biaS= 20

rtio

=

b - a

HR - LR

100 - 20

600 - (-200)

80

800

= 0.1

=

biaS

=

starting point = a

´

rtio

=

E.g.: biaS= 100

rtio

=

b

´

- a

´

HR - LR

20 - 100

600 - (-200)

-80

800

= -0.1

=

=

Example with high absolute alarm

#hy-d

Alarm threshold

#hy-u

On

Off

SP = SL + (rtio • REM) + biaS

SP = REM + (rtio • SL) + bias
SIGN = Remote signal %
SPAN = HR-LR

REM =

SIGN * SPAN

100