8 - Technical Specifications

Features
at 25°C env. temp.

Description

Algorithm

PID with overshoot control or On-off - PID with valve drive algorithm, for controlling motorised positioners

Proportional band (P)

0.5…999.9%

Single action
PID algorithm

Integral time (I)

1…9999 s

OFF

= O

Derivative time (D)

0.1…999.9 s

Error dead band

0.1…10.0 digit

Overshoot control

0.01…1.00

Manual reset

0…100%

Cycle time (Time proportional only)

0.2…100.0 s

Min./Max output limits

0…100% separately adjustable

Soft-start output value

1…100% - Time 1…9999 s

Control mode

Output safety value

-100…100%

Control output hysteresis

0…5% Span in engineering units

On-Off algorithm

Dead band

0.0…5.0%

Double action
PID algorithm
(Heat / Cool)

Cool proportional band (P)

0.5…999.9%

Cool integral time (I)

1…9999 s

OFF

= O

Cool derivative time (D)

0.1…999.9 s

Cool cycle time (Time proportional only) 0.2…100.0 s
Control output high limit

0…100%

Motor travel time

15…600 s

Valve drive PID algorithm
Raise/Stop/Lower

Motor minimum step

to 0.1…5.0%

Control output forcing value

-100…100%

Feedback potentiometer

100

Ω …10kΩ

Control output rate limit

0.01…99.99%/s

OFF

= O

Cool output max. rate

0.01…99.99%/s

OFF

= O

X5-SSI-uk 18-03-2009 17:54 Pagina 65