66

8 - Technical Specifications

Features
at 25°C env. temp.

Description

OP1 - OP2 outputs

SPST Relay N.O., 2A/250Vac (4A/120Vac) for resistive load
Triac, 1A/250Vac for resistive load

Galvanic isolation: 500 Vac/1 min
Short circuit protected
Resolution 12 bit
Accuracy: 0.1 %

OP3 output

SPDT relay N.O., 2A/250Vac (4A/120Vac) for resistive load

Active low

OP4 output

RSPST relay N.O. 2A/250Vac (4A/120Vac) for resistive load

Analog/digital
OP5 and OP6
(option)
outputs

Control or PV/SP
retransmission

Analog:

0/1... 5V, 0…10V, 500

Ω/20mA max.,

0/4... 20mA, 750

Ω/15V max.

Digital:

0/24Vdc ±10%; 30mA max. for solid state relay

AL1 - AL2 - AL3 - AL4
alarms

Hysteresis 0…5% Span in engineering units

Action

Active high

Action type

Deviation threshold

±range

Band threshold

0… range

Absolute threshold

whole range

Special functions

Sensor break, heater break alarm

Acknowledge (latching), activation inhibit (blocking)

Connected to Timer or program (if options installed) (only OP3-OP4)

Setpoint

Local + 3 memorized

Up and down ramps 0.1...999.9 digit/minute or digit/hour (OFF=0)
Low limit: from low range to high limit
High limit: from low limit to high range

Remote only

Local and Remote

Local with trim

Remote with trim

X5-SSI-uk 18-03-2009 17:54 Pagina 66