Strt, Tres, A.man – Super Systems X5 User Manual

Page 62: Keb.i, H.pu, S.p. 1, S.p. 3, Slo.1, F.out, S.p. 2

Advertising
background image

Start-Hold timer

#strt

Start-Hold timer

Reset Out 3

#tres

Reset Output 3 connected to the timer

End timer

#End

Abort timer

62

6 - Commands

6.2

DIGITAL INPUTS
COMMANDS

A function is assigned through
the configuration procedure to
each IL1, IL3 and IL3 digital
input. (see the parameters set-
ting at tab. 10 at page 30).
The configured function is acti-
vated when the digital input (free
voltage contact or open collec-
tor output) is in the On state
(closed). It is deactivated by set-
ting the input to the Off state
(open).
The activation of the function
through the digital input has the
highest priority than through the
keypad or through the serial
communication.

6.2.1 DIGITAL INPUTS COMMANDS FOR LOCAL-REMOTE SETPOINT

Function

Parameter

value

Performed operation

Notes

None

#OFF

Not used

Set manual mode

#A.Man

Automatic

Manual

Keyboard lock

#keb.I

Unlock Locked

With the keypad locked the commands from digital
inputs and serial communications are still operating

PV measure hold

#H.pU

Normal

operation

PV is hold

The value of PV is “frozen” at the time the digital input
goes to the close state

Set Remote mode

#l=r

Local

Remote

1st stored Setpoint

#s.p. 1

Local

1st SP

The permanent closure forces the chosen stored value.
Setpoint modification is not possible.
The impulsive closure, selects the stored value. Setpoint
modification is allowed. If more than one digital input
is selecting a Setpoint, the last to be activated is the
operating one (see page 43)

#s.p. 3

Local

3th SP

Off

On

Setpoint slopes inhibition

#Slo.1

Rate limiting

is active

Normal

operation

When the input is in the on state, the Setpoint is changed
in steps

Output forcing mode

#F.Out

Normal

output

Forced

output

With ON command the output is equal to the forced
value (see page 28)

#s.p. 2

Local

2nd SP

3th stored Setpoint

2nd stored Setpoint

Reactivation of blocking

#bLcK

Reactivation

of blocking

The blocking function is activated on closing the com-
mand from digital inputs

X5-SSI-uk 18-03-2009 17:54 Pagina 62

Advertising