4 - Operation

[C] START-UP DISABLING

∆SP

Disable

SP

On

Off

Start-up

ramp

down

ramp

up

∆SP

threshold

=

SP

± range

Disable

SP

∆SP

On

Off

Start-up

Bloc

Yes

LOOP BREAK ALARM (LBA)

When the controller connection to

the sensor is discontinued or

other faults are detected in the

control loop, AL1 alarm becomes

active after a predefined time of

1... 9999 s from the detection of

the failure (see page 37).

When a sensor failure occours,

the LBA interventrion is immedi-

ate. The alarm state ceases when

the fault condition is no longer

present.

e

In case of ON-OFF control, the

LBA alarm is not active.

[D] ALARM DISABLING AT SENSOR BREAK

PV

Process
variable PV

AL1

#donb

= no

#-FS.H

= 300

°C

Sensor
break

Sensor
replacement

AL1

#donb

= yes

#Sc.Hi

= 500

°C

For those alarms that are configured to be different than LBA, it is possible
to set the parameter

#donb

(disable on break).

Set:

no

To maintain the alarm status when a sensor break is detected.

yes

To disable the alarm intervention when a sensor break is detected. Once
the sensor has been changed, the alarms that were active before the
sensor break are activated again

.

X5-SSI-uk 18-03-2009 17:53 Pagina 33