4 - Operation

Stored Setpoint
Tracking

(see chapter 4.3.2 at page 27)
Two different operation mode
can be set:
A Stand-by mode

# no

The selection of any memorized
SP (SP1, SP2, SP3) does not
overwrite the previous local
Setpoint when the memorized
SP is no longer active. The pre-
vious local SP in unchanged.

B- Tracking mode

#yeS

The use of any memorized SP
(SP1, SP2, SP3) overwrites the
local SP value.
The previous Local Setpoint
value will be lost.

#S.P.tr

Remote Setpoint Bias and Ratio

bias = 20
ratio = 0.1

ratio = –0.1

Remote

signal

Range

600

100

20

0

Remote

Setpoint span

10V

bias = 100

a b

a´ b´

-200

°C

HR

a (b

´ )

b (a

´ )

LR

Remote
Setpoint Ratio

Ratio is the coefficient which
defines the remote Setpoint
span with respect to the input
span.

Remote
Setpoint

Bias defines the starting point of
analog Remote Setpoint in engi-
neering units corresponding to
the low limit (current or voltage)
of the remote signal.

#bias

#rtio

PV

= Process Variable

LR

= PV low limit

HR

= PV high limit

SR

= Remote Setpoint

a (a´) = SR starting point
b (b´) = SR ending point