4 - Operation

Absolute alarm

Active high

é

-fsH

Active low

é

-fsl

hyd

hyu

On

Off

On

Off

Alarm threshold

High range

Low range

Deviation alarm

Active high

Active low

é

-del

hyd

hyu

On

Off

On

Off

SP

Alarm threshold

+ range

- range

é

-deH

Band alarm

Active out

é

-bnd

hyd hyu

On

Off

SP

Alarm threshold

full scale

full scale

hyd hyu

∆SP

∆SP

∆SP

4.3.6 AL1, AL2, AL3, AL4 ALARM CONFIGURATION

[A] OPERATING CONDITIONS

Up to four alarms can be config-

ured: AL1, AL2, AL3 and AL4 (see

page 31).

For each alarm the following selec-

tions can be mode:

A

the type and the operating condi-

tion of the alarm (table 11 page 31)

B

the functionality of the alarm

acknowledge (latching)

#ltch

C

the start-up disabling (blocking)

#bloc

D

alarm inhibition on sensor break

E

the physical output of the alarm

#OpI #Op2 #Op3 #Op4

The outputs can be used for
alarms if they are not used as
control outputs (see par.

3.3.7

page 20).

It is possible to route up to 4 alarm

to a single output (OR of the alarms).

Alarm occurrence display

This function can be enabled by the

configuration software.

Please, read the user manual:

Serial communication and configu-

ration software”.

[B] ALARM ACKNOWLEDGE

FUNCTION

The alarm, once occurred, is

presented on the display until

acknowledged. The acknowledge

operation consists in pressing any

key.

After this operation, the alarm

leaves the alarm state only when

the alarm condition is no longer

present.

Ltch

Yes

275.0

3deH

The type of alarm is presented

flashing, on the front panel in
alternation with the PV value.

The red led of the activated
alarm output is on.