Model 9200 Programmable Dual-loop Controller

SSi Manual SERIES 9200

20 Programmable Dual-loop

cautious not to set the change set point value too low. (E.g. if the furnace controls 1700 in a steady state

at 50% output and you set the change set point value to 40% and the PB value is low, you could find

yourself in a situation where you never see 40% output and remain in a PB only control mode.)

Default PID Parameters for Loop 1(% Carbon) and Loop 2 (Temperature)


Loop 1 Default PID Parameters

Loop 2 Default PID Parameters

Proportional Band: 20

Proportional Band: 4.0

Reset: .10

Reset: 0.10

Rate: 0

Rate: 0

Cycle time: 16

Cycle time: 60

The Cancel key on some of the screens returns you to the previous screen without any changes being

effected. The Esc key takes you back to the Menu Screen.


Event Run Program Setup

Pressing the Enter key takes you to a screen labeled

Event

Run Program (0 to use buffered).

This is used to start a program stored in the 9200, by

contact closure between terminals 21 (Digital In Com) and

17 (Digital In 1). The value entered at program to run will
start with contact closure.
Pressing Enter pops up the Current Value Screen, showing

the current value in the Series 9200. To make an

adjustment, enter the program number, using the numeric

keypad and press the Enter key. This returns you to the

original Event Run Program Screen that now shows the
new program number that you have entered. If you do not

wish to make the change simply press the Esc key which

takes you back to the Event Run Program Screen with NO

change being made to the Event Run Program.


Zone / Load TC Setup

Pressing the Enter key takes you to the following

screen.

This screen is used to set up Load, Monitor
Thermocouples. It is normally used in conjunction

with an ADAM Module to provide information from

the Load Thermocouples. There are three modes of

operation for Load TC Enable. They are Off, On and

On + Alarm. To set the mode on Load TC Enable,

highlight it and press Enter, this will open a new
window, use the blue up and down arrows to

highlight the desired mode then press Enter. This

will enter the selected mode and return you to the

Load TC Screen. By activating a thermocouple, no

conditional soak will start unless the temperature is with the default wait limits of the selected

thermocouple(s).