Model 9200 Programmable Dual-loop Controller

SSi Manual SERIES 9200

23 Programmable Dual-loop

Pressing the Esc key will return you to the Menu Screen.

Zone Assignments

WARNING: This screen should not be changed without consulting SSi at 800-666-4330.

The zone assignment feature allows the SERIES

9200 program to change set points on all

instruments of a multi-zone furnace. The SERIES
9200 has up to five (5) temperature and

atmosphere zone assignments available. The

SERIES 9200 programmer looks for appropriate

zone assignments whenever a set point is to be

sent to the atmosphere or temperature controller.

The temperature set point is sent to every
instrument number in the temperature zone

assignment.

If the

ZONE_OFF

(Zone Offset) opcode had been

used in the program, the set point sent to the

specified zone instrument would have the offset
added. For example, a 3-zone pit furnace where

the bottom zone usually has a higher set point.

The middle zone and the top zone usually have a

lower set point. The bottom zone temperature controller is assigned to zone 1, the middle temperature

controllers to zone 2, and the top zone controller to zone 3.


If the first three steps of a program are as shown below, then the bottom zone set point is 1725, the

middle zones are 1750, and the top zone is 1800.

Step opcode

Temperature Atmosphere

Option

1

ZONE_OFF

50 1

2

ZONE_OFF

25 3

3

SETPT

1750

The first step sets the offset for zone 1 to –25 degrees; therefore, the bottom zone controller would be

sent a set point of 1725 when step 3 is executed. Likewise step 2 sets the offset for zone 4 to 50 degrees.

The top zone then receives a set point of 1800. The middle zone controller would receive the 1750. The
temperature controller displayed on the Status Display is instrument #2. If instrument #2 were the top

zone controller then the Status Display would show the 1800-degree set point.

When using the multi-zone offset feature, the atmosphere and temperature controller assigned as

instruments 1 and 2 should be in zones that will not be offset.