Model 9200 Programmable Dual-loop Controller

SSi Manual SERIES 9200

37 Programmable Dual-loop

on the screen without decimal points. For

example, an offset of 255 would actually

be an offset of 25.5 degrees +, and an
offset of –85 would be an offset of 8.5

degrees -.



Aux SP Configuration

This menu option allows for up to three slave

instruments to have the setpoint retransmitted

from one of the three control loops. This menu
option is typically used to retransmit an alarm

setpoint value to an overtemp controller.

The “Retrans to Slave 1”, “Retrans to Slave 2”,

and “Retrans to Slave 3” menu options each

have four options to select: Off, Loop 1, Loop

2, or Loop 3. These options will allow the user
to select which, if any, values to retransmit to

the selected slave instrument.

The “Setpoint Offset Sl 1”, “Setpoint Offset Sl 2”,

and “Setpoint Offset Sl 3” menu options can be a

number between –32767 and 32767. These
options will allow the user to set the destination

offset for the selected slave instrument.

The “Setpoint Delay Sl 1”, “Setpoint Delay Sl 2”, and “Setpoint Delay Sl 3” menu options can be a number

between –32767 and 32767. These options will allow the user to set the delay, in seconds, before the

setpoint is retransmitted to the selected slave instrument.