Model 9200 Programmable Dual-loop Controller

SSi Manual SERIES 9200

25 Programmable Dual-loop

Highlighting Furnace Name and pressing the Enter key displays an alphanumeric keyboard. Type the

furnace name that you wish to be displayed. Pressing the Enter key returns you to the previous screen
Furnace Name

Pressing the Esc key returns you to the Menu Screen.

Alarm Setup


Highlighting this entry and pressing the Enter key takes you to a two-level screen. The first level allows

you to select the alarm. The second level scrolls through parameters.

Parameter Value
Setpoint
Alarm Type

Hysteresis

A numeric keypad is used to enter the Alarm set point, pressing Enter after selecting the value.

Using the blue up and down arrow keys, select

Alarm Type

press the Enter key. Using the blue up and

down arrow keys select the alarm type from the top and bottom choices.

The top choices are:

The bottom choices are:

Process High

PV 1 Value

Process Low

PV 2 Value

Band, Normally Open

PV 3 Value

Band, Normally Closed

Input 1 Value

Deviation, Normally Open

Input 2 Value

Deviation, Normally Closed

Input 3 Value

PO1 Value

PO2 Value

PO3 Value

After highlighting your choice press the Enter key. This returns you to the previous screen. You should

observe the choice that you made for

Alarm Type

displayed. Using the blue up and down arrow keys

highlight

Hysteresis

and press the Enter key. A numeric pad is displayed to allow you to enter a value.

Press the applicable numeric keys and press Enter. You should be returned to the original Alarm Setup

Screen. If you are configuring more than one alarm, follow the above instructions for each alarm that you

are configuring.

Pressing the Esc key returns you to the Menu

Screen.

Relay Assignments


Pressing the Enter key moves you to the following

screen.