Model 9200 Programmable Dual-loop Controller

SSi Manual SERIES 9200

40 Programmable Dual-loop

DEV_AL

This deviation alarm opcode is used to turn the temperature or atmosphere deviation alarms ON

or OFF.

The option values are:

• OFF, turns off both the temperature and atmosphere alarms;

• TEMPERATURE, turns on the temperature alarm and turns off the atmosphere alarm;

• ATMOSPHERE, turns on the atmosphere alarm and turns off the temperature alarm; and

• BOTH, turns on both the temperature and the atmosphere alarms.

• The band limit can be changed by the

SET_WAIT

opcode.

DOW_INQ

This opcode checks the real time clock for the day of the week. This is useful for performing

operations on a weekly basis on a specific day. The option data is the day of the week, i.e. SUN,

MON, TUE, WED, THU, FRI, and SAT.

EVT_IN

This opcode waits for an input event to be turned ON or OFF depending on the option value. The

option value is the event number followed by either ON or OFF.
If temperature data and/or atmosphere data are specified, they are considered set points and will

be sent to the appropriate controller.

EVT_OUT

The event output opcode turns ON or OFF an output event based upon the option value. The

option value is the event number followed by either ON or OFF.
If temperature data and or atmosphere data are specified, they are considered set points and will

be sent to the appropriate controller.

G_Ramp

This is a guaranteed ramp opcode. The temperature and or atmosphere process value must be

within the deviation band to allow the ramp timer to run. The option values are the ramp time in
hours and minutes, temperature and/or atmosphere set point. The band limit can be changed by

the

SET_WAIT

opcode.

G_SOAK

This is a guaranteed soak opcode. The temperature process value must be within the deviation

band to allow the soak timer to run. The option value is the soak time in hours and minutes. The

band limit can be changed by the

SET_WAIT

opcode.

G_SOAK High

This is a guaranteed soak high opcode. The temperature process value must be above the

deviation band to allow the soak timer to run. The option value is the soak time in hours and

minutes. The band limit can be changed by the

SET_WAIT

opcode.

G_SOAK Low

This is a guaranteed soak low opcode. The temperature process value must be below the

deviation band to allow the soak timer to run. The option value is the soak time in hours and

minutes. The band limit can be changed by the

SET_WAIT

opcode.

GOSUB

The go to subroutine opcode is used to call a program and then return to the calling program.

This is used to execute standard routines that can be used by many programs.

GOSUBs

can be

stacked up to eight levels. The option data is the program number.

HIGH_AL

This opcode is used to enable a high limit alarm on the temperature process and/or the

atmosphere process. The temperature data is the high limit point for the temperature process.

The atmosphere data is the high limit point for the atmosphere process. This alarm remains

active until the program ends.

HIGH_PO

This opcode is used to enable a high limit alarm on the temperature percent output and/or the

atmosphere percent output. The temperature data is the high limit point for the temperature