Model 9200 Programmable Dual-loop Controller

SSi Manual SERIES 9200

31 Programmable Dual-loop

The current value is displayed directly above the bottom row of buttons as Current CJ value: XX.X ° F.


Pressing the Next -> key displays the following screen.

Pressing the Edit button displays a numeric keypad

allowing you to change the Zero Input 1 range

value. Normally terminals 31 and 32 are shorted for

this step.
After entering the new Zero Input value you must

press Calibrate. Pressing the Calibrate key stores

the appropriate value. Pressing the Done will return

you to the User Calibration Screen.

The current value is displayed directly above the
bottom row of buttons as Current Input 1 value:

XX.X UV.

Pressing the Next -> key displays the following

calibration screen:


Pressing the Edit button displays a numeric keypad

allowing you to change the Span Input 1 range

value. Normally terminals 31(-) and 32(+) have

2000 mV applied for this step.

After entering the new Span Input value you must

press Calibrate. Pressing the Calibrate key stores
the appropriate value. Pressing the Done will return

you to the User Calibration Screen.

The current value is displayed directly above the

bottom row of buttons as Current Input 1 value:
XX.X UV.

Pressing the Next -> key displays the following

calibration screen:

Pressing the Edit button displays a numeric keypad

allowing you to change the Zero Input 2-range
value. Normally terminals 29 and 30 are shorted for

this step.

After entering the new Zero Input value you must

press Calibrate. Pressing the Calibrate key stores

the appropriate value. Pressing the Done will return

you to the User Calibration Screen.

The current value is displayed directly above the

bottom row of buttons as Current Input 2 value: XX.X

UV.

Pressing the Next -> key displays the following
calibration screen: