Westermo IDW-90 AT User Manual

Page 69

Advertising
background image

69

6620-3200

*wiop – General IO parameters
This command set the IO parameters.

Syntax: 

 *wiop=<tmin>, <tmax>, <type>, <trig>, <norm>
*wiop=? 
*wiop?

<tmin>

 Min trig pulse time in 10 ms increments [1-255]. 
This parameter sets the minimum time the pulse must be active.  
A pulse shorter than this time will be skipped.

<tmax>

 Max trig pulse time in 10 ms increments [1-255] 
Sets the maximum active width of a pulse, if pulse is longer  
the pulse will be skipped.  
The number of pulses will be calculated when the time  
between pulses is longer than 3 times tmin.

<type>

Trig source and type 

0=NO 

Trigger not used

1=LEVEL 

 Trigger source is the Digital input Level or edge sensitive  
trigger

2=PULSE 

Pulsed trigger used 

3=DCD 

Trigger internally coupled to reflect the DCD signal

4=DTR 

Trigger internally coupled to reflect the DTR signal

0=NO 

Trigger not used

1=HIGH 

Defines that a High level triggers the service   

2=LOW 

Defines that a Low level triggers the service

3=POS 

A positive edge triggers the service.

4=NEG 

A negative edge triggers the service.

<trig>

Trigger level 

0=NO 

Output not used

1=IO operation  Controlled by remote IO Transparent or Out 
2  

Reserved

3=DCD 

 Output will be controlled by DCD. An active DCD  
will activate the output. 

4=DTR 

 Output will be controlled by DTR. An active DTR  
will activate the output.

<norm>

 Normal inactivated state of the output as well as the source  
controlling the output.

Advertising