Cleanness, Cooling – H3C Technologies H3C SecPath L1000-A Load Balancer User Manual

Page 11

Advertising
background image

3

High temperature can accelerate the aging of insulation materials and significantly lower the

reliability and lifespan of the L1000-A.

For the temperature and humidity requirements of the L1000-A, see

Table 1

.

Table 1 Temperature and humidity requirements

Ambient temperature

Ambient relative humidity

Operating
0°C to 45°C (32°F to 113°F)

Nonoperating and storage

–40°C to +70°C (–40°F to +158°F)

Operating
5% to 95%, noncondensing

Nonoperating and storage

5% to 95%, noncondensing

Cleanness

Dust buildup on the chassis might result in electrostatic adsorption, which causes poor contact of metal

components and contact points, especially when indoor relative humidity is low. In the worst case,

electrostatic adsorption can cause communication failure.

Table 2 Dust concentration limit in the equipment room

Substance

Concentration limit (particles/cu m)

Dust particles

≤ 3 x 10

4

(No visible dust on desk in three days)

NOTE:

Dust particle diameter ≥ 5 μm

The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion and

premature aging of components, as shown in

Table 3

.

Table 3 Harmful gas limits in an equipment room

Gas Max.

(mg/m

3

)

SO

2

0.2

H

2

S 0.006

NH

3

0.05

Cl

2

0.01

Cooling

The L1000-A adopts left to right airflow for heat dissipation. Plan the installation site for adequate
ventilation.

Leave at least 10 cm (3.94 in) of clearance at the inlet and outlet air vents.

The installation site has a good cooling system.