Installation precautions, Lightning protection – H3C Technologies H3C SecPath L1000-A Load Balancer User Manual

Page 28

Advertising
background image

20

Figure 18 Installing a lightning protector

(1) Grounding wire

(2) Lightning protector for a network port

(3) Outdoor network cable

(4) Cable connected to the L1000-A

Installation precautions

The performance of the port lightning protector may be affected in the following cases:

The port lightning protector is installed in reverse direction. Connect the IN end to the outdoor
network cable and the OUT end to the network port on the L1000-A.

The port lightning protector is not well grounded. After the connection, use the multimeter to
confirm that the ground wire for the protector is as short as possible to ensure its good contact with

the grounding screw of the L1000-A.

The installed port lighting protectors are not sufficient. If the L1000-A has more than one network
port connected with other devices through cables outdoor, install a lightning protector for each

network port.

Connecting the AC power supply to a power strip

with lightning protection

CAUTION:

Make sure the PE terminal of the power socket has been securely grounded.

If part of the AC power line is routed outdoors, use a power strip with lightning protection to connect the

AC power cord of the L1000-A to the AC power line to protect the L1000-A from being damaged by

lightning strikes.
You can attach the power strip to the rack, workbench, or wall of equipment room.