Precision Digital PD6310 User Manual

Page 10

Advertising
background image

Model PD6210 & PD6310 Batch Controllers

Instruction Manual

10

PASSWORD

Three programmable passwords restrict modification of
programmed settings and two prevent resetting the totals.

Pass 1: Allows use of function keys and digital inputs
Pass 2: Allows use of function keys, digital inputs and editing set/reset points
Pass 3: Restricts all programming, function keys, and digital inputs.
Total Password: Prevents resetting the total manually
Gtotal Password: Prevents resetting the grand total manually

NON-VOLATILE
MEMORY

All programmed settings are stored in non-volatile memory
for a minimum of ten years if power is lost.

POWER
OPTIONS

85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max
or jumper selectable 12/24 VDC

± 10%, 15 W max

FUSE

Required external fuse: UL Recognized, 5 A max, slow
blow; up to 6 controllers may share one 5 A fuse

ISOLATED
TRANSMITTER
POWER SUPPLY

Terminals P+ & P-: 24 VDC

± 10%. 12/24 VDC powered models

selectable for 24, 10, or 5VDC supply (internal jumper J4).
ProVu Series (PD6210):
85-265 VAC models rated @ 200 mA max, 12/24 VDC powered
models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC
supply.
ProtEX-MAX (PD8 Series):
All models transmitter supply rated @ 25mA max.

NORMAL MODE
REJECTION

Greater than 60 dB at 50/60 Hz

ISOLATION

4 kV input/output-to-power line
500 V input-to-output or output-to-P+ supply

OVERVOLTAGE
CATEGORY

Installation Overvoltage Category II:
Local level with smaller transient overvoltages than
Installation Overvoltage Category III.

ENVIRONMENTAL

ProVu Series (PD6210):
Operating temperature range: -40 to 65°C
Storage temperature range: -40 to 85°C
Relative humidity: 0 to 90% non-condensing
ProtEX-MAX (PD8 series):
T6 Class operating temperature range Ta = -40 to 60°C
T5 Class operating temperature range Ta = -40 to 65°C
See LIM8 ProtEX-MAX instruction manual for additional
details.

MAX POWER
DISSIPATION

ProtEX-MAX (PD8 Series): Maximum power dissipation
limited to 15.1 W. See LIM8 ProtEX-MAX instruction
manual for additional details.

CONNECTIONS

Removable screw terminal blocks accept 12 to 22 AWG
wire, RJ45 for external relays, digital I/O, and serial
communication adapters.