Transmitter supply voltage selection (p+, p-), Connections – Precision Digital PD6310 User Manual

Page 22

Advertising
background image

Model PD6210 & PD6310 Batch Controllers

Instruction Manual

22

Transmitter Supply Voltage Selection (P+, P-)

All controllers, including models equipped with the 12/24 VDC power
option, are shipped from the factory configured to provide 24 VDC
power for the transmitter or sensor.
If the transmitter requires 5 or 10 VDC excitation, the internal jumper
J4 must be configured accordingly.
To access the voltage selection jumper:

1. Remove all the connectors.
2. Unscrew the back cover.
3. Slide the back cover about 1 inch.
4. Configure the J4 jumper, located behind the input signal connector,

for the desired excitation voltage as shown.

Figure 5: Transmitter Supply Voltage Selection

6000SensorExcitation

Connections

All connections are made to removable screw terminal connectors
located at the rear of the controller.

!

Caution!


Use copper wire with 60°C or 60/75°C insulation for
all line voltage connections. Observe all safety
regulations. Electrical wiring should be performed in
accordance with all applicable national, state, and
local codes to prevent damage to the controller and
ensure personnel safety.