Model PD6210 & PD6310 Batch Controllers

Instruction Manual

49

Input Calibration Method (InCAL)

There are three methods of calibrating (or scaling) the display to show
the correct engineering units.
• Use

the

Factor

menu to enter a K-Factor. (Pulse input models only.)

• Use

the

Scale

menu to enter the scaling without a signal source.

• Use

the

Calibrate

menu to apply a signal from a signal source.


Note: The K-Factor, Scale, and Calibrate functions are exclusive of
each other. The meter uses the last function programmed. Only one
of these methods can be employed at a time. The Scale and
Calibrate functions can use up to 32 points (default is 2). The
number of points should be set for Scale and Calibrate accordingly
under the Number of Points

(nopts) menu selection prior to scaling

and calibration of the meter, see page 79 for details.

PD6310 Only: K-Factor Calibration (Factor)

The meter may be calibrated using the K-Factor function. Most flowmeter
manufacturers provide this information with the device. Enter the
K-Factor

(Factor) menu and select the decimal point with highest

resolution possible and program the k-factor value (i.e. pulses/gal). The
meter will automatically calculate the flow rate using the k-factor and the
time base selected.