Safety information – Precision Digital PD6310 User Manual

Page 18

Advertising
background image

Model PD6210 & PD6310 Batch Controllers

Instruction Manual

18

Modulated

1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz)

Electrical Fast
Transients

±2kV AC mains, ±1kV other

Electrostatic
Discharge

±4kV contact, ±8kV air

RFI - Conducted

10V, 0.15-80 MHz, 1kHz 80% AM

AC Surge

±2kV Common, ±1kV Differential

Surge

1KV (CM)

Power-Frequency
Magnetic Field

3 A/m 70%V for 0.5 period

Voltage Dips

40%V for 5 & 50 periods
70%V for 25 periods

Voltage
Interruptions

<5%V for 250 periods


Note:

Testing was conducted on PD6200 and PD6300 series meters
installed through the covers of grounded metal enclosures with
cable shields grounded at the point of entry representing
installations designed to optimize EMC performance. All
hardware is identical to the PD6210 and PD6310 controllers.

Declaration of Conformity available at www.predig.com

SAFETY INFORMATION

!

CAUTION

: Read complete

instructions prior to installation
and operation of the controller.

WARNING

: Risk of electric

shock or personal injury.

Warning!

Hazardous voltages exist within enclosure.
Installation and service should be performed only by
trained service personnel.