Model PD6210 & PD6310 Batch Controllers

Instruction Manual

14

Batch Controller Rate/Totalizer Display

RATE DISPLAY
INDICATION

-99999 to 999999, lead zero blanking. “R” LED illuminates
while displaying rate.

BATCH TOTAL &
GRAND TOTAL
DISPLAY

0 to 999,999; automatic lead zero blanking. “T” LED is
illuminated while displaying batch total. “GT” LEDs are
illuminated while displaying grand total. Up to 999,999 for
batch total/preset. Up to 999,999,999 with grand total-
overflow feature. “

oF

” is displayed to the left of grand total

overflow and ▲ LED is illuminated.

BATCH TOTAL
DECIMAL POINT

Up to five decimal places or none:

d.ddddd

, d.dddd, d.ddd, d.dd, d.d,

or

dddddd

Total decimal point is independent of rate decimal point.

TOTALIZER

Calculates total based on rate and field programmable
multiplier to display total in engineering units. Time base
must be selected according to the time units in which the
rate is displayed.

GRAND
TOTALIZER
ROLLOVER

Grand totalizer rolls over when display exceeds
999,999,999. Relay status reflects display.

GRAND TOTAL
ALARMS

Up to seven, user selectable under setup menu. Any set
point can be assigned to grand total and may be
programmed anywhere in the range of the controller for
grand total alarm indication. Relay 1 should always be
assigned to batch.

PROGRAMMABL
E DELAY
ON RELEASE

0.1 and 999.9 seconds; applied to the first relay assigned
to total or grand total.
If the controller is programmed to reset total to zero
automatically when the preset is reached, then a delay will
occur before the total is reset.

GRAND TOTAL
RESET

Via front panel button, external contact closure on digital
inputs, automatically via user selectable preset value and
time delay, or through serial communications.

GRAND TOTAL
RESET
PASSWORD

Grand total passwords may be entered to prevent resetting
the grand total from the front panel.

NON-
RESETTABLE
GRAND TOTAL

The grand total can be programmed as a non-resettable
total by entering the password “050873”.

!

Caution!

Once the Grand Total has been programmed
as “non-resettable” the feature cannot be
disabled.