Non-Latching Relay (Auto)

Automatic reset only

Condition

LED

Relay

Normal

Off

Off

Alarm

On

On

Ack (No effect)

On

On

Normal

Off

Off

In this application, the meter is set up for automatic reset (non-latching
relay). Acknowledging the alarm while it is still present has no effect on
either the LED or the relay. When the alarm finally goes away, the relay
automatically resets and the LED also goes off.

Non-Latching Relay (A-man)

Automatic + manual reset at any time

Condition

LED

Relay

Normal

Off

Off

Alarm

On

On

Normal

Off

Off

Next Alarm

On

On

Ack

On

Off

Normal

Off

Off

In this application, the meter is set up for automatic and manual reset at
any time (non-latching relay). The LED and the relay automatically reset
when the meter returns to the normal condition.
The next time an alarm occurs, the operator acknowledges the alarm
manually while the alarm condition still exists. This causes the relay to
reset, but the LED stays on until the meter returns to the normal
condition.

Latching Relay (LatcH)

Manual reset any time

Condition

LED

Relay

Normal

Off

Off

Alarm

On

On

Ack

Off

Off

In this application, the meter is set up for manual reset at any time.
Acknowledging the alarm even if the alarm condition is still present
resets the relay and turns off the LED.