Alphabetical list of display functions & messages – Precision Digital PD6400 User Manual

Page 89

Advertising
background image

Model PD6400 High Voltage & Current Meter

Instruction Manual

89

Alphabetical List of Display Functions & Messages

Display

Parameter

Action/Setting Description

-99999

Flashing

Underrange condition

999999

display

Overrange condition

20 ma

20 mA output

Enter mA output value read by milliamp
meter with at least 0.001 mA resolution

4 ma

4 mA output

Enter mA output value read by milliamp
meter with at least 0.001 mA resolution

Ack

Acknowledge

Acknowledge relays

Act 1*

Action 1*

Set relay 1 (*through 4) action

Adder

Adder

The channel P math function adder
constant C

Alm 1*

Alarm 1*

Assign digital output to Alarm 1 (*through 8)

Altern

Alternate

Set relay for pump alternation control

A-man

Auto-manual

Set relay for automatic & manual reset

Aout

Analog output

Enter the Analog output scaling menu

Aout 1*

Aout Channel

Analog Output source channel 1 (*through 3)

Aoutpr

Analog output
programming

Enter analog output programming

Assign

Assign

Enter the relay channel assignment menu

Auto

Automatic

Press Enter to set automatic operation

baud

Baud rate

Select baud rate

Big

Upper display

Press Enter to assign the upper display
parameter (default: Ch-V)

Big Hi

Max on Upper
display

Assign digital input to display max on the
upper display (channel V)

Big HL

Max/min Upper
display

Assign digital input to toggle max/min on the
upper display (channel V)

Big Lo

Min on Upper
display

Assign digital input to display min on the
upper display (channel V)

break

Loop break

Set relay condition if loop break detected

bypASs

Bypass

Set filter bypass value

C CAL

Current
calibration

Calibrate 4-20 mA current input (internal
reference source used for scaling the input)

C Hi

Current high

Calibrate high current input (e.g. 20 mA)

C lo

Current low

Calibrate low current input (e.g. 4 mA)

Cal A

Calibrate A

Enter the Calibration menu for channel A

Cal v

Calibrate v

Enter the Calibration menu for channel V

Calib

Calibrate

Calibrate 4-20 mA output (internal reference
source used for scaling the output)

Ch-A*

Channel A*

Channel A (*V or P) selection

Const

Constant

Enter the math function constant menu

Contrl

Control

Enter Control menu to turn relays on/off, set
analog output 1 manually, or return meter to
automatic operation

Advertising