Set door hold open time, Set door behavior at fire alarm – EverFocus EFC--02-1-A User Manual

Page 54

Advertising
background image

46

Press

ENT

to enter Open Time setting. In the menu shown below, press numeric key

1~8 to enter the desired door number in the Door field. (The max number depends

on the actual door modules installed in the controller) Enter the desired door open

time in the OpenTime field: enter minutes as a 3-digit number 0~999, and enter
seconds as a 2-digit number 0~59. Press

ENT

to confirm. Press

to exit without

effecting any change.

Set Door Hold Open Time

Door sensor monitors the open/close status of a door. If normal open is not set by

the system (door is normally considered closed), then door should close after opening

for a while. It is considered abnormal if controller does not receive the door close

signal from door sensor a reasonable amount of time after the door is opened. This

time period is call door hold open time or door over time. According to this setting,

EverAccess controller will determine whether to generate an alarm or not after the

door sensor timeouts. The default value of door hold open time is 5 seconds. The

maximal door hold open time supported by the controller is 999 minutes and 59

seconds.

At the following submenu:

Press

ENT

to enter Door Hold Open Time setting. In the menu shown below, press

numeric key 1~8 to enter the desired door number in the Door field. (The max

number depends on the actual door modules installed in the controller) Enter the

desired door hold open time in the OpenTime field: enter minutes as a 3-digit
number 0~999, and enter seconds as a 2-digit number 0~59. Press

ENT

to confirm.

Press

to exit without effecting any change.

Set Door Behavior at Fire Alarm

The controller allows the user to choose one of two behaviors to occur when a fire

alarm is triggered: fail-safe or fail-secure. Door fail-safe at fire alarm means the door

will be kept unlocked when there is a fire alarm input. Door fail-secure at fire alarm

means the door will be locked when the fire alarm comes in. At the following

submenu:

Door:[_]
OpenTime:___M__S

Over Time
Setting

Door:[_]
OverTime:___M__S

Door Control
at Fire Alarm

CLR

CLR