9 typical sequence, Figure 4 example of typical sequence, Typical sequence – Emerson Autochangeover Controllers AC8 User Manual

Page 15: Figure 4, Example of typical sequence

Advertising
background image

Introduction

7

1.9

Typical Sequence

Figure 4 shows a typical sequence of how the AC8 functions after detecting a change in a monitored

device. Many responses depend on configuration settings. This example shows what happens when a

digital input changes state—assuming the input is defined as alarmable—and when the condition

returns to normal.

Figure 4

Example of typical sequence

ALARMS CLEARED

30-SEP-04

16:24:04

Entry in Alarm Log

(

ALARMS CLEARED

)

DEVICE_1 ALARM
CONTACT CLOSED
30-SEP-04

16:23:04

Entry in Alarm Log

Condition (

ALARM

)

& state (

CONTACT CLOSED

)

The alarm is cleared

(automatically if Unlatched; must be

cleared manually if Latched)

UNIVERSAL MONITOR

05-SEP-02 14:04:13

V5.100.0

PRESS =STATUS/SETUP

ESC

ESC

The LCD stops flashing

RETURN TO NORMAL

The device that triggered the alarm

returns to its normal state.

The horn sounds (audible horn on

the controller board—silence horn by

pressing any key on the LCD keypad)

The LCD flashes

(except during setup)

ALARM CONDITION DETECTED

A device connected to the AC8

changes state.

RESPONSES TO AN ALARM

RETURN-TO-NORMAL SEQUENCE

UNIVERSAL MONITOR

05-SEP-02 14:04:13

V5.100.0

PRESS =STATUS/SETUP

ESC

ESC

DEVICE_1 STARTED
DEVICE_2 STARTED
DEVICE_3 STARTED
DEVICE_4 OFF
30-SEP-04

16:24:06

DEVICE_4 STARTED

30-SEP-04

16:23:10

DEVICE_1 ALARM
CONTACT CLOSED

Entry in Event Log

Status change

(

DEVICE_4 STARTED

)

Entry in Event Log

Actions in response to event

(

DEVICE_1 STARTED,

DEVICE_4 OFF

)

Entry in Active Alarm Log

Condition (

ALARM

)

& state (

CONTACT CLOSED

)

The horn stops sounding

(if user hasn’t silenced it)

User setup determines output

control (for example, the device

in alarm might be disabled and a

standby device set to operate)

Pager numbers are dialed

(up to four configured pagers)

Service number is dialed

(if configured)

Pager numbers & service

number are dialed

Return-to-normal message sent