24 vac output power connections, Figure 6 power wiring to tm115, Figure 7 power wiring to tm230 – Emerson Autochangeover Controllers AC8 User Manual

Page 20: Troubleshooting - transformer module, 2 connecting the battery pack, Obtaining a replacement battery pack, 3 turning on the ac8, Connecting the battery pack, Turning on the ac8, Figure 6

Advertising
background image

Installation

12

24 VAC Output Power Connections

To connect to the 24VAC outputs:
1. Install electrical wiring from device requiring 24VAC power to the Transformer Module.
2. Use copper wire only; proper wiring to use for power is 18, 20 or 22 AWG copper wire. Strip

wire 1/4".

3. There are two 24 VAC output connectors (TB1 and TB2). Terminate wires to the connector as

shown in Figures 6 and 7. TB1 and TB2 are NOT polarity sensitive.

4. Secure the wires to the connector.

Troubleshooting - Transformer Module

A common problem and possible solution are shown in the table below. For further information or if

you have other problems with the unit, consult your local dealer, Liebert representative or the Liebert

Worldwide Support Group.

2.4.2 Connecting the Battery Pack

Before connecting input power to the AC8, connect

the panel’s backup battery (factory-supplied) to the

jumpers so it will begin charging when electrical

power to the AC8 is switched on.

To connect the battery pack, insert the battery

leads into the jumpers as shown at right.

(To disconnect the battery pack, remove the

battery leads from the jumpers.)

Obtaining a Replacement Battery Pack

To obtain a replacement battery pack, contact your

local dealer or Liebert representative. The Liebert

part number is 133455P1.

2.4.3 Turning On the AC8

After connecting the backup battery, turn on the power On/Off switches to the AC8 and the Trans-

former Module (see 1.7 - Controller Board Overview for location of switches).

Figure 6

Power wiring to TM115

Figure 7

Power wiring to TM230

Problem

Possible Solution

Replacement Fuse Part Numbers

24VAC power

not available

from TB1 or TB2

Check fuse for respective

output (TB1 or TB2).

• LITTLEFUSE 218002

or

• BUSSMANN GDC-2A

NOTE
If the battery is not hooked up BEFORE the

AC8 is switched on, it will trigger an alarm.

!

WARNING

To prevent the risk of fire or explosion, replace only with 7.2 V rechargeable NiCad battery pack.

!

CAUTION

Dispose of the battery properly by sending it back to Liebert Corporation or an approved

battery recycling facility.

Wire nuts

connecting

electrical

wiring

24VAC output

(TB1)

Ground

Knockout for

external wiring

TM115

Neutral

(L2)

24VAC output

(TB1)

Ground

Knockout for

external wiring

TM230

Line (L1)

Battery pack connector

Battery pack

Advertising