3.2.2 Connecting Digital Outputs

To connect a digital output:
1. Turn OFF electrical power to the AC8.
2. If necessary, remove a conduit knockout to

permit wire entry into the AC8 enclosure.

3. Bring the wire(s) into the AC8 enclosure

through a conduit knockout or access slot.

4. Loosen the appropriate screw and slip the

stripped end of the wire into the terminal

block.

5. Tighten the screw until it holds the wire

snugly.

3.2.3 Setting the Digital Output Jumpers

Each digital output has an associated jumper to define its operation when power is interrupted and

there is no battery backup to the board. This puts the AC8 in a fail-safe mode and ensures proper

functioning when the board has no power or battery backup.
The AC8 comes from the factory with all digital output jumpers in the OFF position (Normally Open).

The jumper setting for each digital output can be changed to ON (Normally Closed). The settings are

shown in Table 5.

To change the output jumper setting:
1. Find the respective black output jumper on

the circuit board, shown in the illustration,

using the following guide.

2. Decide whether your configuration requires

the jumper to be OFF or ON.

3. Set the jumper as needed:

• Set the jumper to OFF by placing the black jumper on the middle and top pins.
• Set the jumper to ON by placing the black jumper on the middle and bottom pins.

!

CAUTION

To reduce the risk of fire or electric

shock, do not interconnect the outputs

of different Class 2 circuits.

Table 5

Digital output jumper settings

Setting

Output status

(power loss & no battery backup)

OFF

Normally Open

ON

Normally Closed

Jumper

Associated output

PFM1

Output 1

PFM2

Output 2

PFM3

Output 3

PFM4

Output 4

PFM5

Output 5

PFM6

Output 6

PFM7

Output 7

PFM8

Output 8

RELAY

OUTPUTS

TB2:

REV

ONON

PFM5

OFF

(BOTTOM)

(TOP)

4

3

2

1

8

7

6

5

(BOTTOM)

(TOP)

4

3

2

1

8

7

6

5

ON

PFM2

OFF

ON

PF

DIGITAL OUTPUT

TERMINAL BLOCKS

NUMBERING KEYS -

Note numbering begins

with 1 at the bottom and

proceeds up to 4 (green);

and 5 up to 8 (black)

RELAY

OUTPUTS

TB4:

(BOTTOM

2

REV

ONON

PFM5

OFF

(BOTTOM)

(TOP)

4

3

2

1

8

7

6

5

(BOTTOM)

(TOP)

4

3

2

8

7

6

5

ON

PFM2

OFF

NC

C

NO

NC

C

NO

ON

PFM3

OFF

ON

PFM8

OFF

Digital output jumpers

Digital output jumpers

Advertising