System and Control Options

69

7.10.1 Turn Automatic Sequencing On or Off

Use automatic sequencing to set up a schedule for rotation of redundant devices. For example, three

devices might be in operating mode while a fourth device is in standby mode. Every two days, the AC8

returns the standby device to operating mode and places one of the operating devices on standby.
When zones are used, the AC8 manages the rotation sequence for each zone separately, so each zone

might have one device in operating mode and one in standby mode.

Auto sequencing is OFF (deactivated) by default. When auto sequencing is activated (ON or 12h, for a

12-hour interval), the AC8 cycles devices at the specified interval and time of day as follows:

• An output device in Standby mode is returned to Operating mode.
• An output device that is Operating is put in Standby mode.

When more than one device is in Standby mode or turned On, the AC8 performs the operations in a

sequence that rotates the order. For example, in a sequence set up to occur every two days:

• Monday:

Device 1 is placed on Standby, and Devices 2, 3 and 4 operate.

• Wednesday: Device 2 is placed on Standby, and Devices 1, 3 and 4 operate.
• Friday:

Device 3 is placed on Standby, and Devices 1, 2 and 4 operate.

• Sunday:

Device 4 is placed on Standby, and Devices 1, 2 and 3 operate.

To change the auto sequencing settings:
1. From the Setup System Operation Menu, use the arrows

↑↓

to

choose Auto Sequencing, then press Enter

.

Activate or Deactivate
2. In the Activate / Deactivate screen, use the arrows

↑↓

to choose one

of three options:
a. ON for intervals of every 1 to 99 days, then press Enter

and

proceed to Step 3.

b. 12h for an interval of every 12 hours, then press Enter

and

proceed to Step 4.

c. OFF to deactivate auto sequencing, then press Enter

to

return to the previous menu.

Specify Start Time and Interval: Every 1 to 99 Days
3. Select the interval for how often the sequencing should occur in the

Every 03 Days field. The default is 3 days; valid entries range

from 0 to 99 days.

• For each digit, use the arrows

↑↓

to choose a number from 0 to

9, then press Enter

to advance to the next digit.

• When finished, press Enter

to set the time of day.

Specify Start Time: Every 12 Hours
4. Specify the time of day the sequencing should begin in the At 00:00

field. The format is HH:MM for hours and minutes.

• Use the arrows

↑↓

to

choose from available entries for hours

(00-23), then press Enter

to advance to minutes.

• Use the arrows

↑↓

to select minutes (00-59).

• When finished, press Enter

again.

NOTE
Auto sequencing will not function in a zone with any devices defined as Not Used. All outputs

in the zone must be defined as Operating or Standby (see 7.7 - Setup System - Setup

Outputs).

NOTE
The AC8 will not cycle outputs that have been manually forced On or Off through the Override

Output Menu or the hardware switch (see 7.12 - Override Output).

Setup Operation Menu

> AUTO SEQUENCING OFF

STANDBY TESTING OFF
FAILED STANDBY

N

↑↓

=NEXT

=SELECT

HOLD DELAY : 10:00
RESTART

: 00:06

STAGING

: OFF

Activate / Deactivate

AUTO SEQUENCING OFF

↑↓

=NEXT

=EDIT

Set Interval & Start Time

(1- to 99-Day Interval)

AUTO SEQUENCING ON
EVERY 03 DAYS
AT 00:00

↑↓

=NEXT

=EDIT

Set Start Time

(12-Hour Interval)

AUTO SEQUENCING 12h

AT 00:00

↑↓

=NEXT

=EDIT